V2.01
25359_EDEBD
A0279-2320-1_EN
55
Address Words Description
Value
Format
0xD020
2
Byte sequence for float on the Modbus
(1=as defined // 0=reversed)
0-1
unsigned
long
0xD022
2
Frequency correction (0=Auto // 1=50
Hz // 2=60 Hz)
0-2
unsigned
long
0xD024
2
Stage monitoring (0=No, 1=Yes)
0/1
unsigned
long
0xD026
2
Temperature measurement (1=Yes //
0=No)
0/1
unsigned
long
0xD028
2
Fan relay
(1=available // 0=not available)
0/1
unsigned
long
0xD02a
2
Temperature [0.1 °C] that triggers the
fan when the threshold is exceeded
0-700
unsigned
long
0xD02c
2
Temperature [0.1 °C] that causes the fan
to switch off when the value falls below
the threshold
0-700
unsigned
long
0xD02e
2
Temperature [0.1 °C] that triggers the
stages when the value falls below the
threshold
0-700
unsigned
long
0xD030
2
Temperature [0.1 °C] that causes the
stages to switch off when the threshold
is exceeded
0-700
unsigned
long
0xD032
2
0xD034
2
0xD036
2
0xD038
2
0xD03A 2
0xD03C 2
0xD03E
2
Switching performance
0xD042
2
Percentage of smallest available stage
before activation
70-150
unsigned
long
0xD044
2
Percentage of smallest available stage
before stages can be switched off
70-150
unsigned
long
0xD046
2
Time before message "Compensation
unit too small" is displayed [s]
3-3000
unsigned
long
0xD048
2
Idle time after compensation [s]
0-300
unsigned
long
0xD04A 2
unsigned
long
0xD04C 2
Switching interval [s]
0-10
unsigned
long
Data point description for the Modbus protocol
Содержание multicomp F144-MS-1V1C1TI6RO-3
Страница 65: ...Notes 25359_EDEBDA0279 2320 1_EN 65...
Страница 66: ...Notes 25359_EDEBDA0279 2320 1_EN 66...
Страница 67: ...Notes 25359_EDEBDA0279 2320 1_EN 67...