V2.01
25359_EDEBD
A0279-2320-1_EN
12
Control and display panel
Harmonics monitoring:
Activated by set limit
Limit THD:
8%
Stage power:
Not set
Stage power monitored:
Deactivated
Discharge time:
180 seconds
Password:
No password
(9999, meaning all functions are accessible)
Language display:
English
Contrast setting:
4
Brightness setting:
5
Dimmer brightness:
0
Low load limit:
15 mA
Low load delay:
60 minutes
Temperature measurement:
On
Relay 6/12 as stage or fan:
Fan
Alarm relay as error message
or fan:
Error message
Fan switch-on temperature:
> 28 °C
Fan switch-off temperature:
< 23 °C
System switch-off temperature:
> 48°C
System switch-on temperature:
< 43°C
Learning mode menu display:
Off
Key sounds:
On
Error message dialog after reset:
No measuring voltage:
Message and alarm relay
No stage power:
Message and alarm relay
Facility too small:
Message and alarm relay
THD too high:
Message and alarm relay
Operating cycle limit exceeded:
Message and alarm relay
No measuring current:
Message and alarm relay
Low load operation:
Message and alarm relay
Temperature switch-off:
Message and alarm relay