V2.01
25359_EDEBD
A0279-2320-1_EN
40
Description of the display window
Brightness setting:
The LCD brightness can be changed in this submenu. Setting range: 0 to 9.
Dimmer brightness:
The LCD dimming can be changed in this submenu. Setting range: 0 to 9. The bright-
ness is reduced after a set time of 15 minutes.
Low load limit:
In this submenu, the light load detection limit can be changed to either 15 mA or 50
mA.
Low load delay:
The low-load detection delay time of the stage switch-off can be changed in this sub-
menu. It can be varied between 1 and 60 minutes.
Temperature measurement:
In this submenu, the temperature measurement can be activated of deactivated.
Fan relay:
In this submenu, the fan relay can set the last stage relay (stage 6 or 12, depending on
the device version) or assign the alarm relay.
Switching threshold fan on:
In this submenu, the switching threshold for switching on the fan relay can be changed
to between 0°C and 70 °C.
Switching threshold for switching off fan:
In this submenu, the switching threshold for switching the fan relay off can be changed
to between 0°C and 70 °C.
To prevent unnecessary fan switching, a run-on time of 30
minutes is set.
Switching threshold for system switch-off:
In this submenu, the switching threshold for switching off the system can be changed
to between 0°C and 70 °C.
Switching threshold for system switch-on:
In this submenu, the switching threshold for switching on the system can be changed
to between 0°C and 70 °C.
Содержание multicomp F144-MS-1V1C1TI6RO-3
Страница 65: ...Notes 25359_EDEBDA0279 2320 1_EN 65...
Страница 66: ...Notes 25359_EDEBDA0279 2320 1_EN 66...
Страница 67: ...Notes 25359_EDEBDA0279 2320 1_EN 67...