V2.01
25359_EDEBD
A0279-2320-1_EN
28
NOTE
A voltage transformer must be used here with no phase shift between current and volt-
age, as the device is not able to compensate this.
Setting the discharge time:
Checking or, if necessary, changing the discharge time of the capacitor stages is a very
important menu item. You can set the discharge time from 0 to 999 sec. Please make sure
that the correct value is set, otherwise the capacitors could be damaged.
Configuring the capacitor stages:
There are two ways of configuring the capacitor stages. The stages can be configured
manually or using the auto configuration mode.
NOTE
The Auto configuration mode menu will not appear
if the "Learning mode" is deactivated in the "Extras" menu
It is important to set the stage power correctly. You can find the stage power on the
nameplate of the stage or the circuit diagram and then program it manually. In this case,
skip the menu item "Learning mode activate" and enter the power value individually for
each stage.
If you want to activate the learning mode, you have to make sure that all previous sub-
menu parameters have been set correctly.
To activate learning mode, press
U
, change the setting to Yes by pressing
V
, then press
X
to confirm.
The auto configuration then automatically sets the stage powers and discharge times,
but these values need to be checked once the learning process has been completed to
ensure that they are correct.
NOTE
If an error occurs in auto configuration mode (harmonics exceeding the limit, measuring
voltage too high, missing measuring voltage), the process is interrupted and "Auto con-
figuration mode – Error" is displayed. Auto configuration mode can be restarted once the
cause of the error has been rectified.
Description of the display window