V2.01
25359_EDEBD
A0279-2320-1_EN
9
Functional principle
The settings are saved on an EEPROM so that they are not lost in the event of a power
failure.
The measuring cycle of the controller used to record the necessary network parameters
takes approx. 20 ms.
NOTE
Limit for overvoltage switch-off = measuring v 10% (taking the measuring volt-
age ratio into account). This value cannot be changed and serves to protect the compen-
sation system.
In the event of an error, the compensation stages are switched off. The alarm relay switch-
es and "Overvoltage" is displayed.
CAUTION
The discharge times are automatically predefined for the following programmed stage
powers. However, these must be checked and corrected if they differ from the capacitor
specifications.
Capacitor power
Discharge resistance
Discharge time
0.1 kvar – 9.9 kvar
300 kOhm
60 seconds
10 kvar – 19.9 kvar
300 kOhm
120 seconds
20 kvar and above
300 kOhm
180 seconds