MULTICAL® 62
TECHNICAL DESCRIPTION
Ka st up A/“ •
Technical
Des iptio •
5512-1036-GB_
D •
.2016
71
Furthermore the module has two extra pulse inputs, see paragraph 9.8
–
concerning the function of
pulse inputs VA and VB. The module must be powered by 24 VAC.
Pressure transmitter requirements:
… A,
-wire, loop-powered, loop voltage max. 16 VDC
(e.g. type CTL from Baumer A/S)
11.2.5
/ … A
analog outputs (67-00-23) (PCB 5550-1005)
The odule has t o a ti e a alog outputs, hi h a e i di iduall o figu ed at … A o …
mA. Furthermore, the outputs can be configured for a specific measuring value as well as the required
range scaling.
All values on the two analog outputs are updated every 10 seconds. The total response time
–
incl.
response time of the flow meter, calculator and digital to analog conversion
–
may have duration of
30-40 seconds. This response time must be taken into account, when the analog outputs are used for
purposes other than remote viewing. The module shall be mounted in MULTICAL® 62. It cannot be
used separately with flowmeters.
It must be powered by 24 VAC. Configuration is done through 'Base module' menu in METERTOOL.