Installation and operating instructions
6.15 Parameter settings
6.15.1 Setting absolute setpoint temperature or ± 3 K
Parameter P36
It may be necessary in office or hotel applications for the system operator to
specify a base setpoint. The user has the option of changing the setpoint
temperature by ± 3 K to compensate for any different perception of room
temperature.
Alternatively the setpoint can be set in absolute values.
Parameter P36 is used to configure the setpoint setting.
Use parameter P01 to configure the base setpoint for the “Setpoint setting
3 K”.
Function
P36
Setpoint setting
0 = Absolute setpoint setting
1 = Setpoint setting ± 3 K
Function
P01
Base setpoint for setpoint entry ± 3 K
Parameter P36=0
Setting of “absolute” setpoint temperature
Parameter P36=1
Setting of setpoint temperature ± 3 K
When the parameters are set
P37=1 Display setpoint temperature
P36=1 Setpoint setting ± 3 K
no setpoint is shown in the standard display!