85
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
6.17 Control PCB parameter list
Function
Standard
Min.
Max.
Unit
KaCool D AF
(9000265)
P000 Software version
V1.19
0
255
-
-
P001 Base setpoint for setpoint entry ± 3 K
22
8
32
°C
22
P002 Switching on/off hysteresis for valves
3
0
255
K/10
10
P003 Neutral zone in a 4-pipe system (only in automatic mode)
3
0
255
K/10
5
P004 Cooling without fan assistance (natural convection)
0
0
255
K/10
0
P005 Heating without fan assistance (natural convection)
5
0
255
K/10
3
P006 Fan On/Off hysteresis (only in ventilation mode)
5
0
255
K/10
5
P007 P-band, heating
15
0
100
K/10
17
P008 P-band, cooling
20
0
100
K/10
20
P009 Offset to the base setpoint for setpoint input ± 3K
3
0
10
K
3
P010 Clip-on sensor: Limit temperature to activate fan stages 1 and 2 in heating mode
29
0
255
°C
26
P011 Clip-on sensor: Limit temperature to activate fan stages 3 and 4 in heating mode
31
0
255
°C
28
P012 Clip-on sensor: Limit temperature to activate fan stage 5 in heating mode
33
0
255
°C
30
P013 Clip-on sensor: hysteresis for limit temperatures P010, P011, P012, P014
10
0
255
K/10
10
P014 Clip-on sensor: limit value temperature to activate the fan stages in cooling mode
18
0
255
°C
18
P015 Function of input AI1
0
0
19
-
0
P016 Function of input AI2
0
0
19
-
0
P017 Function of input AI3
0
0
9
-
0
P018 Raise temperature of cooling setpoint in Eco mode
30
0
255
K/10
30
P019 Lower temperature of heating setpoint in Eco mode
30
0
255
K/10
30
P020 ADC limit coefficient
6
0
15
-
6
P021 ADC average coefficient
6
0
15
-
6
P022 Activation/deactivation of sun symbol in Comfort mode
0
0
1
-
0
P023 Difference for compensation during cooling
0
-99
127
K/10
0
P024 Coefficient for compensation during heating
0
-20
20
1/10
0
P025 Difference for compensation during heating
0
-99
127
K/10
0
P026 Coefficient for compensation during heating
0
-20
20
1/10
0
P027 Fan setting: maximum run-time for manual fan mode
0
0
255
Min.
0
P028 Flushing function: Fan stage during the flushing function
2
1
5
-
1
P029 Activation of continuous fan mode
0
0
1
-
0
P030 Ventilate temperature activation
12
0
255
°C
12
P031 Ventilation interval
27
0
255
°C
27
P032 Flushing function: maximum idle time of fan
15
0
255
Min.
15
P033 Flushing function: duration of flushing function
240
0
255
s
120
P034 Flushing function: activation in operating modes
0
0
3
-
3
P035 Time the fan runs at Stage 1 after change of operating mode
0
0
255
s
0
P036 Type of setpoint setting
0
0
1
-
0
P037 Display
1
0
7
-
1
P038 Lock/disable function on control unit
64
0
255
-
72
P039 Function of digital output V2 (in 2-pipe system)
0
0
3
-
0
P040 Valve actuation by means of pulse width modulation
0
0
1
-
0
P041 Reset time of PI controller to actuate the fan in automatic fan mode
0
0
20
Min.
0
P042 Fan setting: lock and activate fan stages
0
0
127
-
0
P043 Function of digital input DI1
1
0
14
-
12