KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
LED on IR receiver
ALARM-LED on receiver
Sensor
Units with IR remote control model have 3 sensors as standard:
T1 Air intake sensor: measures the temperature on the
air intake and is used to determine the air intake or room
temperature.
T2 Water temperature/changeover sensor: determines the
medium temperature for changeover between cooling and
heating mode (with appropriate DIP switch setting)
T3 Heat exchanger sensor: determines the emperature of the
heat exchanger. The temperature needs to guarantee that the
cassette operates within the limits of operation (4-75 °C).
LED lights up blue
Cooling mode active
LED lights up red
Heating mode active
LED off
Off or recirculation mode
LED flashes blue
Window contact open
LED flashes red
Water temperature T2 not reached,
waiting mode
Red LED flashes 2x
Float switch alarm
Condensation water alarm
Red LED flashes 3x
EC fan motor alarm
Red LED flashes 4x
Water temperature alarm
T3 ≥ 75 °C
T3 ≤ 4 °C
Red LED flashes 5x
Temperature sensor (air intake) T1 faulty
Red LED flashes 6x
Temperature sensor (water/changeover) T2
faulty
Red LED flashes 7x
Temperature sensor (heat exchanger) T3 faulty
T2 < 15°C
Cooling mode
T2 > 30°C
Heating mode
15°C < T2 < 30°C
Standby/Service mode