73
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
DIP switch no. 6
There is an option of using the internal sensor in the KaController or an
external room temperature sensor for room temperature control.
DIP switch no. 6 = OFF Room temperature control on a suction/external
room sensor
DIP switch no. 6 = ON
Room temperature control on the internal sensor
of the KaController
Factory setting: 2-pipe system DIP6 = OFF
4-pipe system DIP6 = ON
DIP switch factory settings, KaControl, 2-pipe system, control
configuration -C1
DIP switch factory settings, KaControl, 4-pipe system, control
configuration -C1
DIP switch factory settings, KaControl, 2-pipe
system, control configuration
-C1
DIP switch factory settings, KaControl, 4-pipe
system, control configuration
-C1
DIP
2-pipe
C1
Functions
DIP1
OFF
OFF = ---
ON = 0..10 V actuation by on-site MSR
DIP2
OFF
OFF = ---
ON = Activation by potentiometer 0..100 kOhm
DIP3
OFF
OFF = Clip-on sensor not fitted
ON = Clip-on sensor fitted
DIP4
ON
OFF = 4-pipe or heating/cooling changeover with clip-on sensor
ON = Heating/cooling via DI2
DIP5
OFF
OFF = 2-pipe system
ON = 4-pipe system
DIP6
OFF
OFF = Room control on intake air/ext. room sensor
ON = Room control on sensor in the KaController
DIP
4-pipe
C1
Functions
DIP1
OFF
OFF = ---
ON = 0..10 V actuation by on-site MSR
DIP2
OFF
OFF = ---
ON = Actuation by potentiometer 0...100 kOhm
DIP3
OFF
OFF = Clip-on sensor not fitted
ON = Clip-on sensor fitted
DIP4
OFF
OFF = 4-pipe or heating/cooling changeover with clip-on sensor
ON = Heating/cooling via DI2
DIP5
ON
OFF = 2-pipe system
ON = 4-pipe system
DIP6
ON
OFF = Room control on intake air/ext. room sensor
ON = Room control on sensor in the KaController
1 2 3 4 5 6
1 2 3 4 5 6
ON
ON
With slave units, DIP switch no. 6 must be set to ON if the room
temperature is detected via an external room sensor or the
KaController.