16
.
3.25
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
Chilled water air conditioning system
Installation and operating instructions
4.2 Brief description
The KaCool D AF is a decentralised unit for heating, cooling
and filtering air, including in hotels, offices and business
premises. Thanks to the efficient, extremely quiet fan, the
individual comfort temperature is quickly reached.
Operating mode
Secondary air is drawn into the central part of the cover panel.
The air is routed first through the air intake grille to the filter.
This cleans the secondary air of dust and thus protects the
downstream components from dirt and impurities.
The air is drawn in by the fan, located directly downstream
of the filter and pressed through the copper-aluminium heat
exchanger. Depending on the temperature at which the
medium flows through the heat exchanger, the air is either
cooled or heated in the exchanger.
The air then passes through the outlet air slats into the room.
The outlet air slats can be manually adjusted to the required
direction.
Condensation can be produced at the heat exchanger when
cooling with low water temperatures. This drips onto the
heat exchanger and falls into the condensation tray below.
The condensation collects in a corner here. The condensation
level is monitored by a float switch. The condensation pump
is activated when a certain level is exceeded. A condensation
warning is emitted if a higher level is exceeded.
The valve kits available in the accessories can be connected
to the side of the unit. The units include condensation trays,
which can be installed under the valve kits.
The condensation is guided and drained through the prepared
opening into the condensation tray of the unit.