![Kampmann KaCool D AF Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/kampmann/kacool-d-af/kacool-d-af_installation-and-operating-instructions-manual_3374078095.webp)
95
KaCool D AF –
Comfortable feeling of well-being, thanks to AtmosFeel
3.25
Chilled water air conditioning system
Installation and operating instructions
8.2 Maintenance
The sections below describe maintenance work needed for the
proper and trouble-free operation of the equipment.
If there are signs of increased wear during regular checks,
adjust the required maintenance intervals to the actual wear
and tear. Contact the manufacturer with any questions about
maintenance work and intervals ( Chapter 1.4 “Customer
Service” on page 6).
Interval
Maintenance task
Personnel
As required
Display on room control unit - first read the separate instructions for the room
control unit
Caretaker/User
Regular visual inspection of the fixings for damage
Caretaker/User
Quarterly
Visually inspect the filter and replace if necessary
( Chapter 8.3.1. “Changing the filter” on page 105)
Caretaker/User
Every six months
Clean the inside of the unit
Caretaker/User
Every six months
Check the water-side connections, valves and fittings
Caretaker/User
Every six months
Vent the heat exchanger
Caretaker/User
Every six months
Check the electrical wiring
Caretaker/User
Every six months
Clean the outlet grille and remove dirt from the airflow
Caretaker/User
Every six months
Check the antifreeze, if used
Caretaker/User
Every six months
Maintenance of the condensation pump
Caretaker/User
To remove and fit the filter, proceed as described on page 30.
Clean the filter after removal by using a vacuum cleaner or
pressurized air.
8.2.1 Filter cleaning