Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Powador-protect
NOTE: Configures the grid shutdown via a Powador protect
connected to the „INV OFF“ input of the device.
Powador-protect oper-
ation mode
Auto | On | Off
↻
Auto/On: A Powador-protect is operating in the photovoltaic sys-
tem and is connected to the device at the „INV OFF“ input.
F
Set the operating mode for Powador-protect.
Auto
: The device automatically detects a Powador-protect integrated
into the photovoltaic system.
On
: The digital signal of the Powador-protect must be present at the di-
gital input of the device for the device to begin feed-in.
Off
: The device does not check whether a Powador-protect is integrated
into the PV system.
4
1
2
3
4
3rd party device
NOTE: Configures the grid shutdown via a 3rd party device
connected to the digital input of the device
3rd party device name
F
Enter the name of the 3rd party device.
3rd party device opera-
tion mode
On | Off
F
Select operation mode.
On:
The digital signal of the 3rd party device must be on the device's di-
gital input so that the device does not shut down.
Off
: The device does not check whether a 3rd party device is integrated
into the PV system.
4
1
2
3
4
Password protection
Status
1. Option to set password protection.
2. Confirm the action field.
4
1
2
3
4
SPD monitoring
NOTE: Opportunity to check the overvoltage protection with
appropriate status messages.
4
1
2
3
4
SPD monitoring
Status
Password protection
Status
1. Activate overvoltage protection.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Q on Demand
NOTE: Activate function only with explicit permission of the
network operator. Additional conditions:
- No PID solution connected to the unit.
- Constant voltage regulator in the unit is deactivated
figuration via web user interface [
4
1
2
3
4
Night Shutdown
Check to activate
1. Q on Demand is activated by deactivating the night shutdown.
2. Transfer selection to memory.
3. Observe the information window and activate the function with the
"OK" button if necessary.
NOTE: The currently specified reactive power settings are
used. Power-dependent functions are not used.
NOTE: If AC is disconnected during the night, the function is
only available the next day.
4
1
2
3
4
Relay
NOTE: Opportunity to configure the fault signal relay [ERR].
4
1
2
3
4
Relay
Positive logic | Neg-
ative logic
inactive | active
1. Select the type of logic.
2. Select the form of activity.
3. Confirm the action field.
Manual
Configuration and operation | 9
KACO blueplanet 100 TL3
Page 65
EN