Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Lock-In voltage
10 – 126,6 [%
Unom] / 80 [%
Unom] / 0.1
F
Set the voltage above which control is activated.
4
1
2
3
4
Lock-Out voltage
10 – 126,6 [%
Unom] / 80 [%
Unom] / 0.1
F
Set the voltage below which control is deactivated.
4
1
2
3
4
Power gradient in-
creasing & power
gradient decreasing
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
1. Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
2. Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
4
1
2
3
4
Settling time
1000 – 12000 [ms] /
5000 [ms] / 10
F
Set the settling time in the event of an abrupt change in the reactive
power target value.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F
Specify the number of nodes.
4
1
2
3
4
Node 1- Node 10
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] / 1
F
Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%; for the last
node, the power must be 100%. The power values of the
nodes must increase continuously.
0,3 – 1 [ind/cap] /
1 / 0.001
F
Specify the cos ϕ of the node.
Over-excited | un-
der-excited
Password protection
Status
F
If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited
relates to an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
4
1
2
3
4
Q(U)
NOTE: Define Q(U).
4
1
2
3
4
Lock-In power
0 – 100 [% Slim] /
100 [% Slim] / 1
F
Set the active power as % of rated power above which control is ac-
tivated.
4
1
2
3
4
Lock-Out power
0-20 [% Slim] / 5
[%Slim] / 1
F
Set the active power as % of rated power below which control is de-
activated.