No. Grid
LED
LED
Display on web interface
Status description
Action
Pers
.
73
Standalone grid error
Shutdown since an AC grid is no longer avail-
able. Standalone grid detection is only active
in certain country settings.
Is the grid still
present with all
three phases (fuses
tripped)?
B
75
Self test in progress
No fault message, only a status.
-
-
78
Resid. current shutdown
(AFI)
A static residual current causes the device to
shut down. The shutdown threshold is determ-
ined by the power class and the relevant regu-
lations. For devices in USA/Canada (with UL
certification), the device can be reconnected a
maximum of 4 times within 24h. F78 therefore
stops once the 5th fault is triggered within
24h.
If the fault tends to
occur in the event
of precipitation or
high levels of hu-
midity, this indic-
ates the presence of
an insulation fault
on the DC side of
the plant -> check
the DC cabling in
the plant!
E
79
Insulation measurement
The insulation resistance of the plant is calcu-
lated prior to activation.
Normal device re-
sponse Device is not
permitted to be per-
manently in this
status, however. If it
does -> fault in the
device.
B
80
Insulation meas. not pos-
sible
The insulation measurement cannot be per-
formed because the generator voltage is too
volatile.
If a fault message
appears continu-
ously, arrange for a
service to take
place. (Semicon-
ductor defective)
Check PV module
installation.
E