Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
External
NOTE: The output power of the device can be set permanently
to a lower value than the maximum output power by the ex-
ternal power limitation.
4
1
2
3
4
Power Limitation
Status
F
Specify the activation status.
4
1
2
3
4
AC fallback active
power
0 – 100 [%Plim] /
100 [%Plim] / 1
F
Set fallback power.
Specifies the standard power in the event of a communication failure. If
no active power command is received within the configured fallback
time, the device sets the power to the configured fallback power.
4
1
2
3
4
Fallback time
0 – 43200 [s] /
300 [s] / 1
F
Set the fallback time for the external power specification.
WARNING! After the set fallback time, external (RS485 or
Modbus) specifications for cos-phi, Q and P are reset to the
respective set fallback value (cos-phi constant, Q-con-stant or
fallback power).
NOTE: If the fallback time is set to 0s, external settings for
cos-phi, Q and P are not reset (operation continues with the
last received setpoint).
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200 – 60000 [ms] /
1000 [ms] / 10
Password protection
Status
1. Specify the settling time.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Power Rampup
Power rampup gradi-
ent
NOTE: Power ramp-up is used to ramp up the power gradu-
ally. More detailed information at
4
1
2
3
4
Gradient
1 – 600 [% / min] /
10 [% / min] / 1
F
Set increase.
4
1
2
3
4
Rampup on every con-
nect
Rampup on first con-
nect
Rampup after grid fail-
ure
Status
1. Activate option.
2. Activate optional password protection.
3. Confirm action field.
9 | Configuration and operation
Manual
KACO blueplanet 100 TL3
Page 58
EN