Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Voltage
NOTE: Option to monitor the voltage shutdown.
4
1
2
3
4
Trip undervoltage mon-
itoring
Status
F
Activate if necessary.
4
1
2
3
4
Number of trip under-
voltage levels
1- 5 / 2 / 1
F
Specify the number of support levels.
4
1
2
3
4
Trip undervoltage level
1
10 – 100 [% U
nom
] /
80 [% U
nom
] / 0.1
Trip undervoltage time
level 1
0–120000 [ms] / 1
F
Define range and trip-off time.
4
1
2
3
4
Trip undervoltage level
2 – 5
10 – 100 [% U
nom
] /
45 [% U
nom
] / 0.1
Trip undervoltage time
level 2 – 5
0–120000 [ms] / 1
4
1
2
3
4
Trip overvoltage monit-
oring
Status
F
Activate if necessary.
4
1
2
3
4
Number of trip over-
voltage levels
1- 5 / 2 / 1
F
Specify the number of support levels.
4
1
2
3
4
Trip overvoltage level 1
100 – 125 [% U
nom
] /
110.1 [% U
nom
] /
0.1
Trip overvoltage time
level 1
0–120000 [ms] / 1
1. Define range and trip-off time.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Trip overvoltage level 2
– 5
100 – 125 [% U
nom
]
114.8 [% U
nom
] /
0.1
Trip overvoltage time
level 2 bis 5
0–120000 [ms] / 1
Passwortschutz
Status
Manual
Configuration and operation | 9
KACO blueplanet 100 TL3
Page 55
EN