Electrical connection
Operating Instructions KACO blueplanet 29.0TL3
Page 27
EN
Authorised electrician
NOTE
All signal cables for interfaces must be professionally encased up to the connection using the
insulation tube provided before fitting the cable.
1
2
Figure 35: Insert the cable for interfaces
Key
1
Cable fitting (M25) for feeding the Ethernet cable
through.
2
Cable fitting (M16) for feeding the signal cable
through.
Insert the cable for interfaces
ඣ
Open the housing and secure the door with the latch lever provided.
1.
Loosen the cable fitting for feeding the Ethernet cable through.
2. Loosen and remove the cover of the cable fitting.
3. Remove the sealing insert.
4. Thread the connection cable through the cover of the cable fitting and the sealing insert.
5. Insert the sealing insert into the cable fitting.
6. Loosen the cable fitting for feeding the signal cable through.
7. Pass the casing provided around the signal cable (RS485/ERR/Inverter OFF).
8. Insert the signal cable.
NOTE: Run the
casing right up to the connection point. Proceed with cable laying.
1
3
2
Figure 36: Lay the cables for interfaces
Key
1
Ethernet cables
3
Cable ties
2
Threaded stud bolts
Laying the cable for interfaces
ඣ
Open the housing and secure the door with the latch lever provided.
ඣ
Lay the Ethernet cables as per the illustration above.
1.
Fix the encased signal cable to the threaded stud bolts.
2. Lay all the interface cables so that they are not under tension and the housing door has a full range of motion.
»
Proceed with the connection of the cables.