Configuration and Operation
Operating Instructions KACO blueplanet 29.0TL3
Page 45
EN
Country-spec.
Setting
Menu
level
Display/
setting
Action in this menu/meaning
4
1
2
3
3
Minimum cos-phi Q1
and Q4
NOTE:
In the event of a significant voltage deviation,
the maximum reactive power adjustment range can
be limited by a minimum cos φ in order to prevent an
excessive reactive power supply and, as a result, a sig-
nificant reduction in the maximum effective power that
can be fed in.
"
Enter the minimum cos-phi factor for quadrants 1
and 4.
4
1
2
3
3
Priority mode
"
Set priority for reactive power - Q or active power
- P.
NOTE:
When it comes to P priority, the reactive power
adjustment range is limited subject to the effective
power that is currently available and fed in.
4
1
2
3
3
Active curve
"
Select the active curve for regulation.
NOTE:
Up to 4 characteristic curves can be configured
independently and one of them can be activated for
regulation each time.
4
1
2
3
3
Resetting the curve
"
Reset active curve to the default setting.
All countries
4
1
2
3
3
Number of nodes
NOTE:
The maximum number of configurable nodes
depends on the selected grid type.
"
Specify the number of nodes for the reactive power
characteristic curve.
4
1
2
3
3
1st, ... ,10th node
"
Specify the reactive power in %Snom for the 1st , ...
,10th node.
NOTE:
The voltage values of the nodes must increase
continuously. For voltages below the 1st node and volt-
ages above the last node, the reactive power value of
the 1st or last node is used each time.
"
If a reactive power not equal to 1 is selected:
Select the type of phase shift (under-excited
(inductive load) /over-excited (capacitive load)).
All countries
4
1
2
3
1
Extended
standalone grid
detection
NOTE:
Grid operators require shutdown of the inverter
with standalone grid detection.
"
Open the menu: Press the right arrow button or
the Enter button.
4
1
2
3
2
Operation mode
"
Select the type of detection using the right arrow
button.
4
1
2
3
3
OFF
"
Disables standalone grid recognition.
4
1
2
3
3
ROCOF
"
Activate passive grid influence by application of a
frequency.
4
1
2
3
3
Extended ROCOF
"
Activate active grid influence by additional reactive
power feed-in.
4
1
2
3
3
Frequency shift
"
Activate frequency shift.
4
1
2
3
2
ROCOF threshold
"
Specify threshold value for ROCOF (if ROCOF or
Extended ROCOF is active).