Configuration and Operation
Operating Instructions KACO blueplanet 29.0TL3
Page 41
EN
Country-spec.
Setting
Menu
level
Display/
setting
Action in this menu/meaning
All countries
4
1
2
3
1
Activation
condition
NOTE:
The inverter checks mains voltage and fre-
quency. The grid feed operation begins if the measured
values are within the set ranges.
"
Set minimum and maximum values for switching
on.
4
1
2
3
1
Connection time
"
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
4
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage
is present.
"
Set the starting voltage.
4
1
2
3
1
SPD monitoring
NOTE:
Please refer to the application note on our
home page if you install the overvoltage protection by
yourself.
Allows monitoring of the overvoltage protection.
"
Activate overvoltage protection.
NOTE:
By activating, an overvoltage protection test is
carried out with an appropriate status message.
4
1
2
3
1
Constant volt. con-
trol
NOTE:
Possibility to deactivate the MPP seek mode in
order to operate the device with a constant DC voltage.
"
Activate or deactivate the constant voltage
controller.
"
Set value for constant voltage control.
4
1
2
3
1
Power
limitation
NOTE:
The output power of the inverter can be set per-
manently to a lower value than the maximum output
power by the internal power limitation.
This may be necessary in order to limit the maximum
power rating of the system at the grid connection
point, upon the grid operator's request.
The value can be protected from the very first power
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specific pass-
word.
1. Activate or deactivate password protection
2. Specify activation status (on/off )
3. Specify limit value for maximum feed-in
power
4. Confirm the entry with the Enter button.
All countries
4
1
2
3
1
Powador-protect
NOTE:
Configures the support for grid shutdown by a
Powador-protect connected to the digital input of the
inverter.
ඣ
For Auto/On: A Powador-protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
"
Auto: The inverter automatically detects a Pow-
ador-protect integrated into the photovoltaic
system.
"
On: The digital signal of the Powador-protect must
be present at the digital input of the inverter for
the inverter to begin feed-in.
"
Off: The inverter does not check whether a Pow-
ador-protect is integrated into the PV system.