background image

Country-
spec. Set-
tings

Men
u
level

Display/
Setting

Action in this menu/meaning

 Operating mode –

On | Off

Setting | Manual |Pre-
defined zero current

Setting: Manual

All parameters can be configured independently.

Setting: Predefined zero current

Dynamic grid support active on account of immunity to interference and
zero current feed-in. During a voltage incident, the current in the in-
verter is reduced to zero.

All parameters are pre-configured, only the activation threshold for zero
current has to be configured.

Priority – Reactive cur-
rent limitation | Active
current priority

Priority: Reactive current priority

Dynamic grid support active on account of immunity to interference and
fast feeding of residual current. The inverter feeds additional reactive
current according to the formulae (2) and (4).

Priority: Effective current priority

Dynamic grid support active on account of immunity to interference and
fast feeding with active current priority. The inverter feeds in as much
active power as available. If, as a result of this, the maximum continuous
current is not achieved, the device supplies additional reactive current
according to the formulae (2) and (4) up to the limit of continuous cur-
rent.

Zero current undervolt-
age threshold

Zero current threshold
over voltage

 0 – 80 [% Unom] / 

10 [% Unom] /   0.1

 108 – 129 [%

Unom] /   125 [%
Unom] /   0.1

If one or more phase/phase or phase/neutral conductor voltages move
above the configured threshold, the inverter changes to zero current
mode. The total current is regulated to virtually zero.

Reference voltage

 80 – 110 [% Unom] /
 100 [% Unom] / 

0.1 [Unom]

Nominal value of the phase/neutral conductor voltage used as a refer-
ence voltage for formula (1) and (3). Adjustable in the range from level 1
undervoltage protection to level 1 overvoltage protection.

Constant k negative se-
quence dip

Constant k negative se-
quence swell

 k 0 – 10 /   2 / 

0.1

Amplification factor for the negative sequence used in the calculation of
the reactive current using formulae (2) and (4) Can be configured inde-
pendently for drops and spikes.

Constant k positive se-
quence dip &

Constant k positive se-
quence swell

 k 0 – 10 /  2 /   0.1

Amplification factor for the negative sequence used in the calculation of
the reactive current using formulae (2) and (4) Can be configured inde-
pendently for drops and spikes.

Dead band

 2 – 120 [% Uref] / 

10.0 [% Uref] /   0.1

Dynamic grid support through fast feeding of residual current activated
in the case of voltage events with a voltage change greater than the
dead band.

10 | Specifications

Manual

KACO blueplanet 110 TL3 KACO blueplanet 125 TL3

Page 90

EN-US

Содержание blueplanet 110 TL3

Страница 1: ...KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 These instructions form part of the product and must be carefully read observed and stored in a place which is freely accessible at all times Authorize...

Страница 2: ...ce for ease of reading Trademarks All brand and product names used in this document are trademarks or registered trademarks A lack of identifi cation does not mean that a product or designation logo i...

Страница 3: ...faces 30 7 10 Sealing the connection area 33 8 Start up 34 8 1 Conditions 34 8 2 Preconditions relating to standards 34 8 3 Network topologies 35 8 4 Start up options 36 9 Configuration and operation...

Страница 4: ...4 1001897 KACO blueplanet 92 0 TL3 M1 WM OD IIG0 KACO blueplanet 92 0 TL3 M1 WM OD IIGX 1001785 1001898 KACO blueplanet 105 TL3 M1 WM OD IIG0 KACO blueplanet 105 TL3 M1 WM OD IIGX 1001941 1001951 KACO...

Страница 5: ...nger Failure to observe this warning may lead to serious bodily injury or death CAUTION Low risk hazard Failure to observe this warning will lead to minor or moderate bodily injury CAUTION Risk of dam...

Страница 6: ...ic requirements details see manual Grid Support Interactive Inverter Max Backfeed Current 0 A Conf to UL 1741 UL 62109 1 Cert to CSA C22 2 No 107 1 CAN CSA Std C22 2 No 62019 1 CAN CSA Std C22 2 No 62...

Страница 7: ...the electrical connections Remove all jewellery from wrists and fingers Ensure that the testing equipment is in safe operating condition Modifications to the surroundings of the device must comply wi...

Страница 8: ...cifications See section 4 3 Page 14 Operation outside the specifications prescribed by the manufacturer Overvoltage of more than at the DC connection 1500 V Device modification Standalone mode 2 2 Pro...

Страница 9: ...feed through 4 Status indicator 9 DC isolator switch not present in S version 5 AC connection cable feed through 3 2 1 Mechanical components DC isolator switch not present in S version The DC isolator...

Страница 10: ...ensive configurations are also possible via the web interface Inverter Off input DRM 0 for Australia In addition to the safety functions the internal interface switches can also be actuated via the In...

Страница 11: ...DC isolator switch enables disconnection on the DC side Switch box A switch box with integrated DC isolator switch enables dis connection from the inverter on the DC side Inverter with circuit breake...

Страница 12: ...ed overvoltage pro tection will work correctly if the ambient temperature is 40 C 4 The Max input current is the maximal theoretical value for operation with full power when the feed in power is low T...

Страница 13: ...25 TL3 US Max efficiency 99 1 98 98 European efficiency 98 8 98 73 CEC efficiency 98 8 98 70 Self consumption Standby 10 W Infeed from 200 W Protection class over voltage category I III AC II DC Trans...

Страница 14: ...Bending box 1001917 absolutely mandatory for UL market Accessory articles KACO order no Bending box 1001917 AC inverter input plate kit 1001882 double row 1001906 M63 32 AC inverter overvoltage pro te...

Страница 15: ...u if necessary 5 2 Transporting the unit CAUTION Hazard due to impact risk of breakage to the device 1 Pack the device securely for transport 2 Transport the device using the intended carrying handles...

Страница 16: ...ion 5 Immediately remove dirt especially on vents 6 Failure to observe these instructions may result in damage to the device which is not covered by the warranty NOTE Access by maintenance personnel f...

Страница 17: ...he body is overloaded Lifting the device for transportation to change location and during installation can lead to injuries e g spinal injuries 1 Only lift the device using the openings provided 2 The...

Страница 18: ...e device may be seriously injured 1 Use only fixing materials that are suitable for the mounting base The fastening materials supplied are only to be used for masonry and concrete 2 Only install the d...

Страница 19: ...ise the device vertically using the openings provided 2 Use a climbing aid for the chosen installation height 3 Wear safety gloves and safety shoes when lifting and lowering the device NOTE Power redu...

Страница 20: ...tection against theft The device is installed Proceed with the electrical installation CAUTION Damage to property due to condensation build up If the device is pre assembled moisture can get into the...

Страница 21: ...d on the mount Wipe any moisture off the frame of the housing cover using a cloth 1 Undo the 6 screws 2 and carefully remove the housing cover 1 T_25 2 Be careful not to damage or soil the seals or op...

Страница 22: ...DC side Max cable cross section 450 kcmil Min cable cross section in accordance with local installation standards Diameter of cable for cable fitting 0 63 1 10 inch Cable lug dimension b width max 1 6...

Страница 23: ...the insulation from the AC cables 6 Strip the insulation from individual wires for L1 L2 L3 ABC and PE ground so that the strand and insulation can be pressed into the cable lug shaft CAUTION Risk of...

Страница 24: ...lectricity grid If the residual current monitoring unit malfunctions the device is immediately disconnected from the public grid on all poles The functionality of integrated RCMU shall be observed in...

Страница 25: ...as to the location of this fault 3 Rectify any faults before taking further measurements 4 Measure the electrical resistance between the protective earth PE and the positive cable of the PV generator...

Страница 26: ...is intended exclusively for PV generators Other sources fall within the scope of im proper operation e g batteries 3 Only touch the PV generator cables on the insulation Do not touch the exposed ends...

Страница 27: ...bing over the uninsulated crimping point and a maximum of 0 79 0 0 08 inch over the cable insulation and shrink fit using manual shrink fit ting equipment 9 Secure the input plate using the 4 screws T...

Страница 28: ...C surge protec tion device F Position and secure intermediate plug in frame onto AC surge protection socket NOTE Different AC surge protection modules are used The designation on the PCB must match th...

Страница 29: ...ix the output cable to the cable guide 8 Insert the RS485 overvoltage protection module into the base 9 Ensure that the protective elements are properly secured Proceed with the installation of the pr...

Страница 30: ...e device from electrostatic discharge Components inside the unit can be damaged beyond repair by static discharge 1 Observe the ESD protective measures 2 Earth yourself before touching a component by...

Страница 31: ...through the sealing insert NOTE Use a suitable category 7 network cable The maximum distance between two devices is 100 m 328 ft The Ethernet switch allows for the repeater function and supports auto...

Страница 32: ...must be connected to all inverters and to the data monitor unit in the same way Wire A to wire A and wire B to wire B GND to GND 5 Tighten the cable fittings W_20 13 27 In Ibs NOTE When using the RS48...

Страница 33: ...Loosen the cable fittings W_20 2 Thread the connection cables through the cable fittings 3 Connect wire A from COM 11 on the terminal of the protective device to the terminal marked INV OFF on the fir...

Страница 34: ...ce into operation The following functions are only available via the WEB interface 1 Initial start up 2 Parameterization 3 Resetting the device to its factory defaults NOTE We recommend using an up to...

Страница 35: ...ver Database Server App Server XMPP Service User HTTP S 1 2 5 3 4 6 7 8 9 10 Fig 42 Segmentation of a plant 1 Gateway VPN 3G 4G router 6 Network segment switch 2 Main network switch 7 Inverter 3 FO sw...

Страница 36: ...r actively Option 2 Local start up with pre arranged configuration Installation technician uses a USB memory stick that contains a pre prepared device configuration The device imports these settings a...

Страница 37: ...us SC BP125 Ethernet Port 1 DHCP Ethernet Notebook Ethernet Notebook Ethernet Port 0 Static IP Inverter Notebook Notebook Ethernet Ethernet Fig 44 Start up via Ethernet Application The planned network...

Страница 38: ...tion 9 2 Page 43 2 Bei g ltiger Konfiguration werden die Parameter bertragen Once the parameters have been adopted and the device has been restarted the device is put into opera tion 8 4 4 Starting u...

Страница 39: ...ure provides an example of the structure of a plant segment consisting of a Segment Controller and a certain number of KACO devices with string combiner SC combinations MOD BUS RTU RS485 DC DC MOD BUS...

Страница 40: ...devices in the segments can be reached via Ether net using the Segment Controller assigned to them All Segment Controllers are monitored by a central Plant Controller Required components Notebook with...

Страница 41: ...y configuration A language has been selected 1 Select Country and Grid type from the dropdown menu 2 Confirm the action field Pressing the Next button will take you to the next installation step Fig 4...

Страница 42: ...models If there are concerns over security write access can be deac tivated 1 Specify the Modbus port and determine Read write access 2 Confirm the action field Pressing the Next button will take you...

Страница 43: ...operating states The LEDs can display the following states LED illuminated LED flashing LED not illuminated Operating status LED Icon Description Start The green Operation lights up when AC and DC vo...

Страница 44: ...remains inactive until the USB stick is removed or then performs a reset and restarts Procedure has com menced initialisa tion The green Operating LED and the green Feed in LED are flashing quickly y...

Страница 45: ...AC Export Current meassurements Language Main Menu cumulative yield Selected meassurements String Combiner Opitonal Operation mode Previous page Current power Status history Activity indicators for co...

Страница 46: ...action Yield Monitor Configuration Info Collapse all Expand all Parameters Overview Parameters Grid Parameters Interfaces Power Control Power Limitation Internal External System Maintenance Reactive...

Страница 47: ...ce you have entered the password protection will be disabled for all protected grid parameters including the password protection setting for 15 minutes Protection is reactivated automatically after th...

Страница 48: ...y F Select a week The web interface shows the selected data 4 1 2 3 4 Month display Displays the recorded operating data graphically F Select a month The web interface shows the selected data 4 1 2 3...

Страница 49: ...ected to the device are entered in the segment controller Baud rate number of data acquisition units 9600 8n1 1 Specify transmission and detection intervals 2 Enter the number of data acquisition unit...

Страница 50: ...Ride Through NOTE The device supports dynamic grid stabilization Fault Ride Through NOTICE More detailed information at See sec tion 10 3 Page 88 4 1 2 3 4 Operating mode On Off F Select a control pr...

Страница 51: ...hreshold for zero current mode If one or more phase phase or phase neutral conductor voltages move below or above the configured threshold the inverter changes to zero current mode The total current i...

Страница 52: ...F 4 1 2 3 4 ROCOF proportionality factor 5000 5000 0 00 Hz s 1 Status 1 Define the proportionality factor 2 Confirm the action field 4 1 2 3 4 Ramp Rate Limitation NOTE Opportunity to limit power in t...

Страница 53: ...m 0 1 Max conn voltage af ter grid failure 90 125 Unom 0 1 F Specify switch on voltage range after grid error 4 1 2 3 4 Min conn frequency after grid failure 45 65 Hz 0 01 Max conn frequency after gri...

Страница 54: ...quency or voltage 4 1 2 3 4 Generic parameters NOTE Opportunity to activate standard protective shutdown 4 1 2 3 4 Trip with intentional delay Status 1 If necessary activate delayed trip off 2 Activat...

Страница 55: ...65 Hz 47 5 Hz 0 01 Trip underfrequency time level 2 5 0 1000000 ms 100 1 4 1 2 3 4 Trip overfrequency monitoring Status F Activate if necessary 4 1 2 3 4 Number of trip overfre quency levels 1 5 2 1...

Страница 56: ...100 Unom 45 Unom 0 1 Trip undervoltage time level 2 5 0 120000 ms 1 4 1 2 3 4 Trip overvoltage moni toring Status F Activate if necessary 4 1 2 3 4 Number of trip over voltage levels 1 5 2 1 F Specif...

Страница 57: ...ntioned menu items are filled in Off Apply settings manually 4 1 2 3 4 IP Address F Allocate a unique IPv4 address in the network 4 1 2 3 4 Subnet Mask F Assign a subnet mask 4 1 2 3 4 Default gateway...

Страница 58: ...ger F Assign a unique RS485 bus address to the device Bus termination is carried out on the HMI board by means of a dip switch F Confirm the action field 4 1 2 3 4 Power Control Input screens for powe...

Страница 59: ...cos phi constant Q con stant or fallback power NOTE If the fallback time is set to 0s external settings for cos phi Q and P are not reset operation continues with the last received setpoint 4 1 2 3 4...

Страница 60: ...an abrupt change in the reactive power target value e g caused by a voltage jump 2 Activate optional password protection 3 Confirm the action field 4 1 2 3 4 Q constant NOTE Define the Q constant 4 1...

Страница 61: ...th node as a percentage of the maximum power NOTE For the 1st node the power must be 0 for the last node the power must be 100 The power values of the nodes must increase continuously 0 3 1 ind cap 1...

Страница 62: ...reactive power Q or active power P NOTE When it comes to P priority the reactive power adjust ment range is limited subject to the active power that is cur rently available and fed in 4 1 2 3 4 Number...

Страница 63: ...cy exceeds the configured activation threshold PM NOTE A drop in the range of 2 to 12 corresponds to a gradient in the range of 100 Hz to 16 Hz 4 1 2 3 4 Steigung bei fallender Frequenz 0 200 Pref Hz...

Страница 64: ...the action field 4 1 2 3 4 Voltage dependent NOTE Activate voltage dependent power reduction in the P U menu 4 1 2 3 4 Operation mode OFF ON F Regelverfahren aktivieren Off Deactivates dynamic grid s...

Страница 65: ...tection 3 Confirm the action field 4 1 2 3 4 Features Functions NOTE Input screens for advanced device functions 4 1 2 3 4 External grid protection disconnection NOTE Option to detect the external gri...

Страница 66: ...interface Page 49 4 1 2 3 4 Night Shutdown Check to activate 1 Q on Demand is activated by deactivating the night shutdown 2 Transfer selection to memory 3 Observe the information window and activate...

Страница 67: ...e selected measurement data to the storage device or move the data selectively 4 1 2 3 4 Parameter Manage ment NOTE Option to reset configured values and the import and export of specific parameters 4...

Страница 68: ...tion wizard was completed appears 4 1 2 3 4 Service NOTE Opportunity to specify the service interval 4 1 2 3 4 Service Log NOTE Display of all logged installations You should also add all maintenance...

Страница 69: ...Assign a subnet mask 6 Assign a gateway 7 Assign DNS server 8 Save your settings 9 6 Carry out firmware update NOTE The DC power supply must be guaranteed during initial start up 12 The sequence of t...

Страница 70: ...successfully completed Device with multifunction buttons Ensure power supply 1 Insert USB stick into the USB socket of the device 2 Use multifunction buttons to load a firmware See section 9 8 Page 7...

Страница 71: ...are flashing slowly and in tandem 1 sec this indicates that a function has been completed successfully If the Fault LED is flashing slowly 1 sec this indicates that a function has not been completed s...

Страница 72: ...USB stick has been removed the device reboots and features the updated data NOTE If a button is not pressed within 15 secs no valid file found Procedure is aborted USB stick can be re moved NOTE Proc...

Страница 73: ...e grid NOTE If a button is not pressed within 15 secs Procedure aborted Disconnecting the device from the grid using the multi function buttons Action step sequence LB RB Notifications function F Pres...

Страница 74: ...or various devices bp 87 0 TL3 Voltage UN 380V bp 92 0 TL3 Voltage UN 400V bp 105 TL3 Voltage UN 400V bp 125 TL3 Voltage UN 600V bp 137 TL3 Voltage UN 600V bp 150 TL3 Voltage UN 660V bp 155 TL3 Voltag...

Страница 75: ...R T Over load capability Fig 68 Apparent power subject to the grid voltage for bp 125 TL3 1 P p u Q P u 0 6 0 4 0 2 0 1 0 8 1 2 0 6 0 6 1 0 0 UN 600V at 600V at 570V at 540V at 510V underexcited over...

Страница 76: ...range for bp 110 TL3 US Qmax Smax 580 S p u Snom U V 0 6 0 4 0 2 0 1 0 8 1 2 380 500 340 300 420 460 540 Nominal capability OVRT Under voltage derating U V R T Fig 78 Apparent power subject to the gri...

Страница 77: ...er than the configured Tau 200 ms by way of a defined gradient or settling time this gradient or settling time must be implemented in the system control Parameter Setting Refer ence Description cos ph...

Страница 78: ...creasing gradient Timeout VArPcT_RvrtTms 0 1000 s Sets the time after which the inverter if it does not receive a new reactive power specification falls back to the previously valid reactive power pro...

Страница 79: ...wer factor Over excited un der excited Reactive power mode Under excited relates to inductive load over ex cited relates to capacitive load Power gradient in creasing power gra dient decreasing 1 65 5...

Страница 80: ...vent of a change in the cos set value With a change of the active power or the lock in and lock out voltage the cos is changed according to a PT 1 characteristic curve with a settling time of 5 Tau Nu...

Страница 81: ...In the event of a significant voltage deviation the maximum reactive power adjustment range can be limited by a minimum cos in order to prevent an excessive reactive power supply and as a result a si...

Страница 82: ...hods described below the specified target value at the inverter s connection terminals is adjusted using a stationary deviation of the reactive power of maximum 2 N SN The transient response of the co...

Страница 83: ...econd solution must be applied for all other inverters 10 2 3 Voltage dependent power reduction P U If it is not possible to compensate adequately for voltage increase in the upstream distribution net...

Страница 84: ...ing volt age Deactivation gradient 0 65 534 min 100 min 1 If the available power is above the actual output at the time of deactiva tion the power increase back to the maximum power is limited The lim...

Страница 85: ...erters must assist with frequency stability in the grid If the grid frequency leaves the normal toler ance range e g 200 mHz the grid is in a critical state In the event of overfrequency there is a ge...

Страница 86: ...n mandatory conges tion management of the grid operator and market control this needs to be implemented in the site specific plant control infrastructure 52 0 51 5 51 0 50 5 50 2 100 PM 60 PM Pref PM...

Страница 87: ...abled if the frequency returns to the range between the minimum and maximum deactivation threshold and remains within this range for the duration of the deactivation time P f intentional delay 0 5 000...

Страница 88: ...e grid or not Protective settings take the upper hand over the capacity of immunity to interference 10 3 1 Dynamic grid support by way of immunity to interference Interference immunity against undervo...

Страница 89: ...inci dent has occurred Responses to changes in the voltage during the incident or to the voltage recovery at the end of the incident take place with the same dynamic The formula for calculating the dy...

Страница 90: ...continuous cur rent Zero current undervolt age threshold Zero current threshold over voltage 0 80 Unom 10 Unom 0 1 108 129 Unom 125 Unom 0 1 If one or more phase phase or phase neutral conductor volt...

Страница 91: ...of residual current is limited to permit a defined proportion of active power components Minimum support time 1 000 15 000 ms 5 000 ms 10 If due to a voltage jump in accordance with formula 1 and the...

Страница 92: ...the ramp time WMaxLimPct_RvrtTms in the SunSpec model is specified as 0 s then the internal output gradient is used Otherwise the set value will be used Irrespective of the communication protocol use...

Страница 93: ...ls simultaneously after they have been switched off by grid protection a soft start up is usually only required for start up after a device has been switched off by grid protection The soft start up i...

Страница 94: ...sure is used in a distribution grid and the deactivated part of the grid remains live as an is land reclosure will likely happen during phase displacement which might cause damage to rotating ma chine...

Страница 95: ...the ROCOF of the grid exceeds the configured disconnection threshold of stage 1 for the configured dis connection time the device switches to zero current mode If the ROCOF of the grid exceeds the con...

Страница 96: ...f feed in operation renewed use of the Q on Demand function is only possible after proper feed in operation with sufficient DC supply The existing deactivated night shutdown also remains active The fo...

Страница 97: ...t in touch with our customer service team Only carry out maintenance activities that are described here 2 Log each maintenance activity in the Service menu item Service log exception User interface Se...

Страница 98: ...aning agents and ensure that no other components come into contact with fluids Cleaning completed if necessary remount the fans 1 2 mm 2 3x Fig 99 Cleaning the cooling fins from above 1 2 4x Fig 100 C...

Страница 99: ...and carefully press it in 2 Insert the fastening screws into the cover on both sides and tighten them _T20 17 70 In Ibs You may now start up the device See section 8 Page 34 2 Fig 103 Fitting the cov...

Страница 100: ...1 DC base 2 DC overvoltage protection module 3 slots 3 Jumper 11 5 Shutting down for maintenance troubleshooting Shutdown sequence 1 Switch off the grid voltage by turning off the external circuit bre...

Страница 101: ...tion section E Contact the grid operator if the grid failure continues to oc cur E The grid fuse trips Damage to the device s hardware If the grid fuse trips immediately when the device goes into feed...

Страница 102: ...messages Fault LED red Status Explanation LED FS fault status The fault relay has switched On Feed in was ended due to a fault OS operating status The fault relay releases again Off The device feeds...

Страница 103: ...g grid feed Should only be re garded as an error if one of the self test rou tines gets stuck If the device re mains in this status continuously de spite adequate DC voltage this indi cates a device f...

Страница 104: ...tiva tion time is I Check PE cabling the cause is gener ally faulty cabling to earth Often occurs during rainfall in the case of faulty ca bling Measure the insulation resistance of the system E 20 Po...

Страница 105: ...the DC generator is too high The PV generator is configured incorrectly Check PV voltage using suitable mea suring equipment Are strings con nected in series in stead of in parallel E 41 Grid failure...

Страница 106: ...heck connection cabling E 49 Grid failure overfrequency Measured value for grid frequency is below the permitted limit This limit is country spe cific See action in the event of a fault 48 E 50 Grid f...

Страница 107: ...dication on display behaves in the same way as normal feed in mode status 4 therefore no flashing This is a require ment from the grid operator 64 Output current limitation Power limitation as the max...

Страница 108: ...ps once the 5th fault is triggered within 24h If the fault tends to occur in the event of precipitation or high levels of hu midity this indi cates the presence of an insulation fault on the DC side o...

Страница 109: ...1 See action in the event of an error 81 E 84 Protection shutdown DC link undervoltage This message appears if the minimum value of the DC link voltage is not reached If the device stops feeding in th...

Страница 110: ...contact the ser vice department B E 101 Temperature plausibility er ror The individual temperatures in the device are compared with one another This fault occurs if a certain limit value is exceeded...

Страница 111: ...PV mod ules Contact your authorised electri cian E 119 DC overvoltage 2 PV voltage above permissible limit values Re wire PV mod ules Contact your authorised electri cian E 125 Relay control fault Th...

Страница 112: ...or is demagnetised prior to feed in If this is not possible this error message ap pears Device error de tected 180 Pre synchronisation not pos sible Adequate voltage pre synchronization with the AC gr...

Страница 113: ...n in the event of a fault 189 See action in the event of a fault 189 193 Semiconductor module 2 in channel B defective See description in the event of a fault 189 See action in the event of a fault 18...

Страница 114: ...and TripZone shutdown Disconnect the AC and DC supply Wait 1 minute and switch back on B 224 External limitation This is a relative specification of the desired active power adjustment Check EMS Redu...

Страница 115: ...ection It has been ensured that there is no AC DC voltage present Remove the housing cover and put it aside 1 Detach cables L1 L2 L3 from the AC connection terminal W_17 2 Detach the PE line from the...

Страница 116: ...ice from being lifted off the mount 2 Use the lateral openings and lift the device off the mount The device has been removed Proceed with packaging 12 5 Packaging the device The device has been uninst...