Activation threshold
with underfrequency:
40 – 50 [Hz] / 40
[Hz] / 0.01
Activation threshold
with overfrequency:
50 – 60 [Hz] /
50.02 [Hz] / 0.01
Activation threshold (f1) underfrequency:
Determines the frequency threshold for activating the function in case
of underfrequency incidents. The active power adjustment is activated if
the frequency falls below the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency rises above the
configured value.
Activation threshold (f1) overfrequency:
Determines the frequency threshold for activating the function in case
of overfrequency incidents. The active power adjustment is activated if
the frequency rises above the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency falls below the
configured value.
Threshold Area lower
limit [Hz]
40 – 50 [Hz] / 47.5
[%/Hz] / 0.01
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation
time.
Threshold Area upper
limit [Hz]
50 – 60 [Hz] / 50.5
[Hz] / 0.01
P(f) Deaktivierungszeit
0 – 6,000,000 [ms] /
0 [ms] 1
Only evaluated in mode 1.
The function is disabled if the frequency returns to the range between
the minimum and maximum deactivation threshold and remains within
this range for the duration of the deactivation time.
P(f) intentional delay
0 – 5,000 [ms] / 0
[ms] 1
The activation of the function based on the activation threshold is de-
layed by the configured time.
Note 1: This function is considered to be critical for the stability of the
transmission grid and is therefore forbidden by many domestic grid con-
nection directives.
Note 2: This function is stipulated as a requirement by some domestic
grid connection directives in order to prevent any negative impact on is-
land detection. However, P(f) has no negative impact on KACO's en-
hanced island detection.
P(f) settling time
200 – 2,000 [ms] /
200 [ms] 1
Determines the dynamic behaviour in the event of a change in the ac-
tive power limit. In the event of a change in frequency, the active power
is altered subject to a PT-1 characteristic curve using a settling time of 5
Tau.
The settling time is overlaid with the increasing and decreasing gradient.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
0 – 65,534 [%/Min] /
65,534 [%/min] /
1
Specifies the dynamic response on changing the active power for power
increase and decrease. With a voltage change, the active power is
changed with the specified gradient.
Note:
The gradient is overlaid with the settling time.
Manual
Specifications | 10
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3