Figure 61: Removing a Fan Module from a QFX5220-128C
g051170
NOTE:
When a fan module is removed, the CLI message Fan/Blower is Absent is logged in the
system log, and the system raises a minor alarm.
How to Remove a Fan Module in a QFX5220
The fan modules in a QFX5220 are hot-removable and hot-insertable field-replaceable units (FRUs); you
can remove and replace them without powering off the switch or disrupting switch functions.
CAUTION:
To ensure proper airflow, keep a failed fan module in place until you have a
replacement fan module at hand. Do not run the device with an open fan tray slot for an
extended amount of time.
NOTE:
The fan module provides FRU-to-port or port-to-FRU airflow depending on the switch
product variant you purchase.
Before you install a fan module in a QFX5220, ensure that you have taken the necessary precautions to
prevent electrostatic discharge (ESD) damage (see
“Prevention of Electrostatic Discharge Damage” on
).