Table 33: Parts Required for Connecting an EX Series Switch to Earth Ground
(Continued)
Switch
Earthing
Terminal
Location
Grounding
Cable
Requirements
Grounding Lug
Specifications
Screws and
Washers
Additional
Information
EX8216
Two earthing
terminals:
•
Left side
of the
chassis
•
Rear
panel of
the
chassis
NOTE: You
must use
only one of
the two
protective
earthing
terminals.
2 AWG
(33.6 mm²),
minimum 90° C
wire, or as
permitted by
the local code
Panduit LCD2-14A-
Q or equivalent
—provided
•
Two ¼ -20 x
0.5 in.
screws with
#¼” split-
washer
—provided
•
Two #¼” flat
washers—
provided
EX9204,
EX9208,
and
EX9214
Rear panel of
the chassis
One 6 AWG
(13.3 mm²),
minimum 90° C
wire, or one
that complies
with the local
code
Thomas& Betts
LCN6-14 or
equivalent—
provided
•
Two ¼ -20
x 0.5 in.
screws with
#¼” split-
washer—
provided
•
Two #¼” flat
washers—
provided
See
Cable and Lug
Specifications for
EX9200 Switches
88