15. If the power supply is installed correctly and functioning normally, the input status LED labeled AC
and output status LED labeled DC on the power supply faceplate are on and steadily lit green, and
the alarm LED (labeled !) is not lit.
16. On the external management device, monitor the startup process to verify that the switch has
booted properly.
SEE ALSO
Power Supplies in an EX9251 Switch | 23
Connecting DC Power to an EX9251 Switch and Powering on the Switch
Before you begin connecting DC power to an EX9251 switch:
• Ensure that you have taken the necessary precautions to prevent electrostatic discharge (ESD)
damage (see
Prevention of Electrostatic Discharge Damage
).
• Ensure that you have connected the switch chassis to earth ground.
CAUTION: To meet safety and electromagnetic interference (EMI) requirements and to
ensure proper operation, you must connect EX9251 switches to earth ground before
you connect them to power. For installations that require a separate grounding
conductor to the chassis, use the protective earthing terminal on the switch chassis to
connect to earth ground. For instructions on connecting an EX9251 switch to ground
using a separate grounding conductor, see
Connect Earth Ground to an EX Series
Switch
.
• Install DC power supplies in the chassis. See
"Installing a DC Power Supply in an EX9251 Switch" on
.
Ensure that you have the following parts and tools available to connect DC power to an EX9251 switch:
• An ESD wrist strap
• DC power source cables (minimum 12 AWG (2.5 mm²), minimum 60°C wire or as permitted by local
code)
• Two ring lugs (Molex 01907000969 or equivalent)—provided with the switch
• An external management device
95