EN
70
Operating Manual: FRWM200 – Smoke Alarm Device with Radio Link
there may be no wireless connection. To trou-
bleshoot, proceed as follows:
(1)
Check the distance between the de-
vices; reduce the distance if necessary.
(2)
Put the devices and radio group into
operation again.
f
Restore factory defaults of all devices
(see chapter 10 „Restoring factory
f
Put the devices and radio group into
operation again (see chapter 6 „Initial
commissioning and setting up“ on
page 59).
Defective connection test
Defective connection test
of a radio group
of a radio group
A defective device can be identified within a
radio group by “group connection test" (see
chapter 9.1 „Radio group connection test“ on
). If a faulty device is identified, pro
-
ceed as follows to troubleshoot
f
In order to exclude a temporary radio
interference from other radio-based
devices, perform group connection test
on another device.
5
Connection test was successful and all
devices are operational.
or
5
Connection test was not successful, there
is a defective device in the radio group.
f
Reset the defective device to factory set-
tings (see chapter 10 „Restoring factory
f
Remove the defective devices allocation
to the radio group (see chapter 10.1
„Cancelling a device from a radio group“
f
Re-connect radio group with a reduced
number of devices (see chapter 10.1
„Cancelling a device from a radio group“
To add a replacement device to the radio
group, refer to the following chapters:
f
Chapter 7 „Expanding radio group and
f