Operating Manual: FRWM200 – Smoke Alarm Device with Radio Link
EN
53
Rooms with straight ceilings
Rooms with straight ceilings
(slope angle < 20°)
(slope angle < 20°)
0,5
0,5
0,5
1/2
1/2
Fig. 3
Rooms with straight ceilings
Allowed
Not allowed
Note the following for locations in rooms with
straight ceilings:
f
Select the highest mounting point on the
ceilings.
f
Mount the devices horizontally to the
mounting surface.
Narrow spaces or corridors (1-3 m wide)
Narrow spaces or corridors (1-3 m wide)
In addition, observe the following for loca-
tions in narrow rooms or corridors that are
1-3 m wide:
f
Keep the distance of less than 7.5 m
between the front surface (end of the
corridor) and the first device.
f
Keep the distance of less than 15 m
between two devices.
Narrow spaces or corridors (< 1 m wide)
Narrow spaces or corridors (< 1 m wide)
In addition, observe the following for locations
in narrow rooms or corridors that are less
than 1 m wide:
f
Keep distance from surrounding walls
(exception: distance less than 0.5 m).
Narrow spaces or corridors
Narrow spaces or corridors
(floor space < 6 m
(floor space < 6 m
22
))
An exception are narrow rooms and corridors
that have an area of less than 6 m
2
.