Mounting and electrical connection
Ref. no. 2103 REG ES
Page 9
of 44
Connection diagram for current measurement using current transformers
Snap the device onto the DIN rail. The terminals for the mains should be
located at the top.
If the device is operated with external current transformers, then connect
according to Fig. 3.
When connecting the cables to the screw terminals of the device, the neutral
conductor must be connected to the device first. On removal, the neutral
conductor must be disconnected from the device last.
NOTE: A load must always be inserted between the output and the neutral
conductor (>< symbol). The output and neutral conductor may not be
connected without a load.
The mains voltage infeed lines to the primary sides of the current transformers
must be protected according to the primary rated current and the current
rating of the cable with F1, F2, F3 fuses (max. 75 A).
The secondary sides of the current transformers are connected in a single-
pole manner to the mains voltage using a cable to be protected with the rated
current of the energy detector 2103 REG ES. The poles of the secondary
sides of the current transformers are to be connected using the inputs E1, E2
and E3 of the energy detector 2103 REG ES. The cable cross-section must be
2.5 mm
2
.