Application
Ref. no. 2103 REG ES
Page 18
of 44
Object Name
Object
function
Type DPT
Flag
7, 13, 19 Ch
n
MV
Current (rms.)
2 bytes
9.021
CR-T-
Description: The effective value of the channel current strength in
mA
.
Object Name
Object
function
Type DPT
Flag
8, 14,
20, 24
Ch
n
MV
Effective power
4 bytes
14.056
CR-T-
Description: The effective power of the channel in
W
.
Object Name
Object
function
Type DPT
Flag
9, 15,
21, 25
Ch
n
external LV Effective power LV
4 bytes
14.056
CRWT-
Description: The external limit value of the channel's effective power in
W
, at which, if over or undershot, a
monitoring telegram can be transmitted, can be changed using this object. The new limit value is stored
permanently or in the volatile memory, according to the configuration.
Object Name
Object
function
Type DPT
Flag
10, 16,
22, 26
Ch
n
LV,
exceed/below
Effective power
1 bit
1.xxx
C--T-
Description: If the limit value for the effective power is over or undershot, a monitoring telegram can be
transmitted, whose value is "1" on overshooting or "0" on undershooting.
Object Name
Object
function
Type DPT
Flag
11, 17,
23, 27
Ch
n
MV
Reactive power
4 bytes
14.056
CR-T-
Description: The reactive power of the channel in
VAr
.
Object Name
Object
function
Type DPT
Flag
28 MV
Frequency
4
bytes
14.033
CR-T-
Description: The mains frequency in
Hz
.