Application
Ref. no. 2103 REG ES
Page 23
of 44
Object Name
Object
function
Type DPT
Flag
124
Rate
Rate 3 - Costs
4 bytes
13.xxx
CR-T-
Description: The object contains the currently incurred costs for Rate 3. These are calculated from the
counter level of the three-phase current energy counter for Rate 3.
Object Name
Object
function
Type DPT
Flag
125
Rate
Rate 1 - Price
2 bytes
7.xxx
C-WT-
Description: The object can be used to specify a price for Rate 1 via the bus. If a telegram is transmitted to
this object, then the price configured by the ETS is overwritten. However, the price of the Rate will be set
back to the price configured by the ETS on the next ETS download. The transmitted integer value is
interpreted in 0.1 ct/kWh.
Object Name
Object
function
Type DPT
Flag
126
Rate
Rate 2 - Price
2 bytes
7.xxx
C-WT-
Description: The object can be used to specify a price for Rate 2 via the bus. If a telegram is transmitted to
this object, then the price configured by the ETS is overwritten. However, the price of the Rate will be set
back to the price configured by the ETS on the next ETS download. The transmitted integer value is
interpreted in 0.1 ct/kWh.
Object Name
Object
function
Type DPT
Flag
127
Rate
Rate 3 - Price
2 bytes
7.xxx
C-WT-
Description: The object can be used to specify a price for Rate 3 via the bus. If a telegram is transmitted to
this object, then the price configured by the ETS is overwritten. However, the price of the Rate will be set
back to the price configured by the ETS on the next ETS download. The transmitted integer value is
interpreted in 0.1 ct/kWh.