Application
Ref. no. 2103 REG ES
Page 17
of 44
5.3. Object
table
Depending on the configuration, some objects may not be available.
Object Name
Object
function
Type DPT
Flag
0
General
Power saving mode
1 bit
1.003
CRWT-
Description: Power saving mode ("0" = Power saving mode off, "1" = Power saving mode on). In Power
saving mode, no measurements occur and no energy is counted.
Object Name
Object
function
Type DPT
Flag
1 General Time
3
bytes
10.001
C-W-R
Description: Internal clock of the energy counter. The current time must be set for the time-bound
functions after switch-on.
Object Name
Object
function
Type DPT
Flag
2
General
Time Request
1 bit
1.xxx
C--T-
Description: After switch-on, this object can be transmitted with a configurable value, in order to request
the current time from a KNX clock.
Object Name
Object
function
Type DPT
Flag
3 General
In Use
1 bit
1.xxx
C--T-
Description: This object can be transmitted cyclically with a configurable value and represents a status
message for the operation of the energy counter.
Object Name
Object
function
Type DPT
Flag
4
Gen. measure
Request measured values
1 bit
1.xxx
C-W--
Description: On receiving this object with the configurable value, the energy counter sends the measured
values Voltage, Current strength and Frequency.
Object Name
Object
function
Type DPT
Flag
5
Gen. measure
Request power values
1 bit
1.xxx
C-W--
Description: On receiving this object with the configurable value, the energy counter sends the measured
values Active power and Reactive power.
Object Name
Object
function
Type DPT
Flag
6, 12, 18 Ch
n
MV
Voltage (rms.)
2 bytes
9.020
CR-T-
Description: The effective value of the channel voltage in
mV
.