Application
Ref. no. 2103 REG ES
Page 40
of 44
Description:
Values:
Comment:
Send counter on change (Wh)
0
...12720
The following counter levels of the
three-phase current variables can be
transmitted on a change by a
configured value:
Counter level
Counter level, Rate 1
Counter level, Rate 2
Counter level, Rate 3
Setting of the change at which the
counter levels are to be transmitted.
Send current counter on change (Wh)
0
...12720
The following current counter levels of
the three-phase current variables can
be transmitted on a change by a
configured value:
Current counter level, Rate 1
Current counter level, Rate 2
Current counter level, Rate 3
Setting of the change at which the
current counter levels are to be
transmitted.
Current counter Rate 1
Via Rate
parameters
Via trigger objects
Here, it is possible to specify whether
the current counter of the three-phase
current variables for Rate 1 is to be
activated using Rate parameters (i.e.
time or Rate object) or via trigger
objects.
Current counter Rate 1 - Trigger 2
Stop
Continue
If the current counter of the three-phase
current variables for Rate 1 is to be
activated via trigger objects, the
counter is either stopped on receipt of
trigger object 2 or continues counting.
Current counter Rate 2
Via Rate
parameters
Via trigger objects
Here, it is possible to specify whether
the current counter of the three-phase
current variables for Rate 2 is to be
activated using Rate parameters (i.e.
time or Rate object) or via trigger
objects.
Current counter Rate 2 - Trigger 2
Stop
Continue
If the current counter of the three-phase
current variables for Rate 2 is to be
activated via trigger objects, the
counter is either stopped on receipt of
trigger object 2 or continues counting.
Current counter Rate 3
Via Rate
parameters
Via trigger objects
Here, it is possible to specify whether
the current counter of the three-phase
current variables for Rate 3 is to be
activated using Rate parameters (i.e.
time or Rate object) or via trigger
objects.