Application
Ref. no. 2103 REG ES
Page 24
of 44
5.4. Parameters
Depending on the configuration, some setting options may not be available. In these
cases, they are not shown in the ETS.
Description:
Values:
Comment:
→
General
Sending delay after bus voltage return
(s)
2
...255
The automatic transmission of objects
after bus voltage return can be delayed,
in order to reduce the bus load.
Setting of the seconds of the delay
time.
Offset for
¼
-hour counter values (s)
0...
2
...255
The transmission of
¼
-hour counter
values at the end of every
¼
hour can
be delayed, in order to reduce the bus
load, when multiple energy counters
are being used. In the standard setting
"2", for example, the values are
transmitted at hh:00:02, hh:15:02,
hh:30:02, hh:45:02.
Setting of the seconds of the delay
time.
Request time after bus voltage return
Yes
No
Here, it is possible to set whether an
object for requesting the time is
transmitted after a bus voltage return.
Value of communication object 'Time
request'
0
1
The object for requesting the time has
the value specified here.
Send object 'In use'
0
...65535
A status message for the operation of
the energy counter can be transmitted
cyclically.
Setting of the seconds of the cycle time
or switch-off of this function with the
value 0.
Value of object 'In use'
0
1
The status message for the operation
of the energy counter has the value
specified here.
→
Measurement
Nominal frequency
50 Hz
60 Hz
The correct nominal frequency of the
power network must be specified here
for the measurements to be made with
the specified accuracy.
Current range
Direct
measurement 16 A
Transformer
measurement 75 A
Here, it is necessary to set whether the
device is operated with or without
external current transformers.
Appr. comm. object ‚Request measured
values‘
Yes
No
Here, it is possible to enable the object
for requesting the measured values.