Application
Ref. no. 2103 REG ES
Page 31
of 44
Description:
Values:
Comment:
→
Energy counter
Channel 1
Yes
No
Access to the counter values of
Channel 1 can be enabled here.
Channel 2
Yes
No
Access to the counter values of
Channel 2 can be enabled here.
Channel 3
Yes
No
Access to the counter values of
Channel 3 can be enabled here.
3-phase values
Yes
No
Access to the counter values of three-
phase current variables can be enabled
here.
→
Energy counter - Channel 1
Telegram on limit value (
¼
-hour
counter value)
Yes
No
Here, it is possible to set whether a
telegram is transmitted when a limit
value of the
¼
-hour counter value of
Channel 1 is over or undershot.
Accept limit value from bus
Volatile
Permanent
The limit value for the
¼
-hour counter
level of Channel 1 can be overwritten
with an object.
Setting of whether the new limit value
applies until the next reset / bus voltage
failure or permanently overwrites the
value configured with the ETS.
Limit value (Wh)
0
...1060
Specification
of
the limit value for the
¼
-hour counter level of Channel 1
Hysteresis (Wh)
0
...1060
A hysteresis can be configured for the
over or undershooting of a limit value
for the
¼
-hour counter level of Channel
1. On overshooting, the actual limit
value is
Limit value +
½
hysteresis
and, on undershooting,
Limit value -
½
hysteresis.
Specification of the hysteresis for the
¼
-hour counter level of Channel 1.
Counter after ETS download
No reaction
Reset
Here, it is possible to set whether the
counter levels of Channel 1 remain
unchanged after an ETS download or
are reset to 0.