8.4.7 LONG TERM AVERAGING
This function enables or disables averaging of the grease level sensor readings over 7
days. Long term averaging of the measured grease level is intended to prevent short
term changes in measured grease level from causing false clean cycle initiations.
CAL MODE–USE UP/DWN
KEYS TO ENABLE OR
DISBALE LT AVERAGE
LT AVERAGE–DISABLED
Pressing the Up button to enable and Down button to disable long term averaging:
CAL MODE–USE UP/DWN
KEYS TO ENABLE OR
DISBALE LT AVERAGE
LT AVERAGE –ENABLED
8.4.8 SET PUMP TIME
This function sets the run time of the pump during a clean cycle.
CAL MODE-USE UP/DWN
KEYS TO SET PUMP
ON TIME, ENTER TO
XXXXX SECS
Use the Up and Down buttons to set the pump run time in seconds. The maximum is
400 seconds and the minimum is 20 seconds. When the desired run time is displayed,
press the
Pres the Enter button to save the data.
The pump time saved is then displayed as follows:
CAL MODE– PUMP ON
TIME ENTERED
SET TO: XXX SECS
GI-2000 Manual V2.3
Page
34