7.0 MAINTENANCE
WARNING!
Remove power from the
GI-2000 GRD system prior to performing
maintenance operations.
7.1 Solids
Removal
To maintain optimum system performance and accuracy it is important to remove all
solids that have accumulated in the solids interceptor. Do not allow any solids to
build up in the GI-2000.
7.2 Sensor
Maintenance
The GI-2000 requires that the grease level sensor be periodically cleaned of grease
or debris that may be stuck to the sensor.
JOSAM recommends the grease level sensor be cleaned every time the interceptor
tank is pumped out. As a minimum, the tank probe should be cleaned every 3
months.
Grease level sensor cleaning can be accomplished by wiping the probe with a soft
cloth or sponge. A degreaser (i.e. dish washing soap, etc.) may also be used.
Warning:
Do not use an abrasive material (i.e. scouring pad, steel wool, etc.) to clean
the tank probe as this may damage the grease level sensor protective covering. Do
not bend the grease level sensor during cleaning.
7.3 Periodic
Calibration
Recalibration of the system is not typically required after the grease level sensor has
been cleaned. JOSAM recommends that system calibration be performed once a year
after the interceptor tank is pumped out.
7.4 Controller
Maintenance
The controller requires no scheduled maintenance.
7.5 Maintenance
Log
It is recommended that owner maintain a daily maintenance log to insure GI-2000
maximum performance. See sample Maintenance Log on next page.
GI-2000 Manual V2.3
Page
15