At this point fill the tank to the second calibration mark. Typically the water level is at the
bottom of the outlet pipe.
Next, press the Enter button the display will cycle to:
READING LEVEL TWO
CALIBRATION –WAIT-
This reading will take longer than level one and may take up to several minutes. After
the level calibration is read, the screen cycles to:
LEVEL 2 CAL.
SUCCESSFUL
Display cycles after a few seconds to:
CALIBRATION COMPLETE
RETURNING TO
NO
RMAL OPERATION
The unit then returns after a few seconds to Automatic or Manual display modes.
8.4.4 SET AUTO CLEAN DAYS
This function allows the user to force a clean cycle every 1 to 90 days if no clean cycle
has occurred due to measured grease level. Entering 0 days disables this function.
CAL MODE–USE UP/DWN
KEYS TO SET AUTO
CLEAN DAYS, PRESS
ENTER TO SET XX DAYS
Pressing the enter button:
CAL MODE–AUTO CLEAN
DAYS ENTERED
SET TO: XX DAYS
GI-2000 Manual V2.3
Page
32
The unit returns after a few seconds to automatic or manual display modes