5.7
RECLAIM TANK ALARM
The GI-2000 controller has an optional integrated reclaim tank alarm system designed to
monitor the state of the reclaim tank, alert the user when the reclaim tank is full and
prevent overflow of the reclaim tank. The option consists of the following components
provided by Josam:
-
Float switch Assembly
-
Float Switch Cable
The GI-2000 controller will prevent further grease pump out and alert the user as follows:
-
Prior to starting a clean cycle the GI-2000 controller will check the status of the
reclaim tank switch.
-
If a full reclaim tank is detected the clean cycle will be prevented from starting.
-
If a full reclaim tank is detected during a grease pump, the pump will be
immediately stopped.
-
The horn will sound (distinct dual beep verses the standard clean cycle single
beep) to indicate a full reclaim tank situation.
-
The LCD display will also indicate a full reclaim tank situation exists.
The GI-2000 controller alarm will continue to sound periodically and the display the
reclaim tank full alert until the reclaim tank is no longer full.
Note: See Section 8.9 for details on the GI-2000 controller reclaim tank display.
Installation of the GI-2000 reclaim alarm system consists of:
-
Mounting the float switch assembly to the cover of the reclaim tank.
-
Attaching one end of the cable provided to the GI-2000 controller via the
mating connector.
-
Running the cable from the GI2000 controller to a junction box located at the
reclaim tank.
-
Running wires from the float switch assembly to the junction box using a water
tight conduit
Proper operation of the GI-2000 reclaim system can be verified as follows:
-
Manually lift the float on the float switch assembly
-
The GI-2000 controller alarm should immediately sound and the display switch
to the reclaim tank alarm message.
-
Release of the float will stop the GI-2000 alarm and the display will return to
the normal.
GI-2000 Manual V2.3