H. Fuel gas line check
1. Gas type and calorific value of fuel gas corresponds to specification.
2. Gas supply pressure is within acceptable range.
3. Gas shut-off valves for the main burner perform within acceptable range.
4. Close the measuring port valves for gas line.
5. Open the valves for the gas lines.
I. Adjust combustion
1. Manually start each water pump.
2. Confirm the water box covers do not leak while the water pump operates.
3. Stop each water pump manually.
4. Set each water pump operation mode to automatic.
5. Navigate to the Control Panel Setting screen.
6. Press the appropriate Operation Mode button.
7. Connect the service vacuum pump to the absorber purging valve. Press the
purge pump Mg-SW key
ON
button.
8. Purge the non-condensable gas from the absorber. Use the procedure detailed
in the
Maintenance
section of the manual.
9. Open the refrigerant manual blow valve.
10. Navigate to the Control Panel Setting screen.
11. Press the Control Valve Mode
Manual
button (which is in the maintenance
setting interface).
12. Make sure that the Refrigerant Pump
Auto
button is pressed.
13. Press the
OPER.
button on the Control Panel.
14. Check that the following start properly:
a. Solution circulation pump
b. Refrigerant pump
15. Check for abnormal noise or vibration.
16. Confirm that the consumption of fuel gas at low combustion is within
acceptable range.
17. Verify that the concentration of Carbon Monoxide (CO) and Oxygen (O
2
) is
within acceptable range when the exhaust gas is at low combustion.
5
YHAU-CGN/H-CXR(M) Small Direct Fired Absorption Chiller-Heater Checklist
95
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater