Start up
A. Operation Check
1. Press the Control Valve Mode
Auto
button.
2. Check that the capacity control valve works automatically according to the
chilled water outlet temperature.
3. Press the
STOP
button on the Control Panel.
4. Check that the dilution process completes.
5. Press the
OPER.
button on the Control Panel.
6. Operate the chiller-heater for 3 hours or longer.
7. Close the refrigerant manual blow valve.
8. Operate the chiller-heater for an additional hour or longer.
9. Check that the cooling water temperature is controlled within the acceptable
range.
10. Check that the specific gravity of the refrigerant is within the acceptable
range.
11. Check that the chilled water outlet temperature is lower than the chilled water
inlet temperature.
12. Record the running data on the data sheets.
B. Purge Amount Check
1. Verify that the purge amount from the absorber by the additional service
vacuum pump is within acceptable range.
2. Continuously purge from the purge tank by water ejector until the exhausted
non-condensable gas amount reduces and becomes stable.
3. Operate the chiller for about 1 hour without operating the water ejector or the
additional service vacuum pumps.
4. Verify that the amount of purge from the purge tank is within the acceptable
range.
C. Purge System Check
1. Press the Purge Mode
Auto
button.
2. Open the water manual valve for the water ejector valve. Connect the hose to
the water drain system.
D. Remote Operation Check
Confirm that the chiller-heater starts and stops properly using the remote signal.
7
YHAU-CGN/H-CXR(M) Small Direct Fired Absorption Chiller-Heater Checklist
97
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater