Figure 48: Four-wire N:1 connection with user-created cable
The following table contains information regarding the communication specifications needed for
for information about the read command or
Table 20 about the write command.
Table 23: Communication specifications
Communication protocol
Modbus/RTU
Communication path type
RS422/RS485 data length: 8 Bit Stop Bit: 1 Bit Parity: EVEN
Speed: 9600 bps
Connector
D-Sub 9pin
Function code
Read Coil Status: 01
Read Holding Register: 03
Device
Digital Signal: Coil
Analog Signal: Holding Register
Slave equipment address
1
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater
82