T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers 
Installation Instructions

10

Pband

Sets the proportional band used by 
the controller Proportional-Integral 
(PI) control loop.
Default: 

2.0F°/1.1C°

Note:

The proportional band 

default setting of 2.0F°/1.1C° 
provides satisfactory controller 
operation in most instances. A 
proportional band setting other than 
the default is normally used in 
installations where the location of 
the controller is problematic, leading 
to unwanted cycling. An example of 
a problematic installation is a 
wall-mounted controller installed 
between the return and supply air 
feeds, that is directly influenced by 
the supply air stream.

(2):

 2.0F°/1.1C°

(3):

 3.0F°/1.7C°

(4):

 4.0F°/2.2C°

(5):

 5.0F°/2.8C°

(6):

 6.0F°/3.3C°

(7):

 7.0F°/3.9C°

(8):

 8.0F°/4.4C°

Anticycl

Anti-Short Cycle timer sets the 
minimum on/off times for heating 
and cooling.
Default: 

2.0 min

Note:

Set the anti-short cycle timer 

to 0.0 min for equipment that 
already has its own anti-short cycle 
timer.

Range: 

0.0

 to 

5.0 min

 adjustable in 1-minute increments

Heat cph

Sets the maximum number of 
Heating cycles per hour.
Default: 

4.0

Range: 

3.0

 to 

8.0

 cycles per hour

Cool cph

Sets the maximum number of 
Cooling cycles per hour.
Default: 

4.0

Range: 

3.0

 or 

4.0

 cycles per hour

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0F°/1.0C°

Range: 

2.0F°/1.0C°

 to 

4.0F°/2.0C°

 adjustable in 1.0F°/0.5C° 

increments

Fan cont

Determines how the fan is activated 
in response to a call for heating.
Default: 

on

Note:

The 

Fan cont

 parameter 

applies to W1 and W2 when the fan 
is in the Auto mode only. The 

Fan 

cont

 parameter does not affect fan 

operation on a call for cooling 
(Y1 and Y2).

(off):

 The controller does not activate the fan in response to a call 

for heating. The fan is activated by the equipment fan and limit 
control.

(on):

 Enables the controller to activate the fan in response to a call 

for heating.

Fan del

Fan delay extends fan operation 
after a heating or cooling cycle has 
ended.
Default 

off

Note:

The fan delay is only active 

when the fan is in the Auto mode.

(on):

 Extends fan operation by 60 seconds after a heating or cooling 

cycle has ended.

(off):

 No extension of fan operation after a heating or cooling cycle 

has ended.

Table 2:  Installer Configuration Menu  (Part 3 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание T606MSN-4

Страница 1: ...er and open the controller as illustrated in Figure 1 IMPORTANT The T606MSx 4 and T606MSx 4 PIR Series Temperature and Humidity Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designe...

Страница 2: ...controller Note If you need to install the thermostat on an electrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bol...

Страница 3: ...re making electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the T606...

Страница 4: ...ccupancy of the electronic control card inside the equipment configure the relay parameter Aux Cont to the Normally Open N O setting A second relay can be added for additional occupancy input functions 3 The humidifier output uses a half bridge rectifier The control signal reference is the controller power supply common terminal C 4 Electromechanical contacts are used with the digital input Electr...

Страница 5: ... is on The cool LED is on when cooling is on Integrated PIR Sensor T606MSx 4 PIR Series Controllers The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied Programming Overview Three menus ...

Страница 6: ... includes a high limit sequence This sequence allows the use of a remote 0 to 10 VDC humidity sensor to keep the humidifier from saturating the supply air The remote sensor throttles the output of the Proportional plus Integral plus Derivative PID loop if the high limit sensor measures humidity in the duct over the high limit value 85 less the proportional band of the high limit PID loop If no sen...

Страница 7: ...ed strategy If the controller is programmed to be Unoccupied the PIR function does not have an effect on the occupancy strategy The controller automatically switches the occupancy level between Occupied and Unoccupied as required when local movement is sensed In the Occupied mode if no movement is detected beyond the Unocc TM parameter setting the mode changes to Unoccupied Once movement is detect...

Страница 8: ...splay Menu and when the message is displayed the backlight momentarily lights up The input can be configured to the Selection Options included in Table 2 Table 2 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unauthorized access to the Installer Configuration Menu Default 0 Note ...

Страница 9: ...ccess Clock Setting2 Access Access Access Permanent Hold2 Access No Access No Access Pwr del3 Sets the delay time period at controller powerup or each time power is removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Frost pr Provides a minimum heating set...

Страница 10: ...er of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cycles per hour Deadband Sets the minimum deadband between the heating and cooling setpoints Default 2 0F 1 0C Range 2 0F 1 0C to 4 0F 2 0C adjustable in 1 0F 0 5C increments Fan cont Determines how the fan is activated in response to a...

Страница 11: ...5 0F 2 5C adjustable in 1 0F 0 5C increments H stage Reverts the operation of a two stage controller to a single stage controller when the second heating stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation of a two stage controller to a single stage controller when the second cooling stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages H lock Disables...

Страница 12: ...cupied temperature at the start of the Occupied schedule off Disabled provides the desired occupied temperature after the Occupied schedule begins RH LT5 Sets minimum outside air temperature for RH setpoint reset Default 20 F 29 C Range 40 F 40 C to 15 F 9 5 C RH HT Sets maximum outside air temperature for RH setpoint reset Default 32 F 0 C Range 20 F 6 5 C to 55 F 13 C HL Sp Sets high humidity le...

Страница 13: ...chedule menu display Any other setting enables schedules and the Schedule menu T606MSP 4 and T606MSP 4 PIR models 2 T606MSP 4 and T606MSP 4 PIR models 3 When adjusting the numeric value press the UP DOWN arrow key to change the value by single increments press and hold the UP DOWN arrow key to change the numeric value in increments of ten 4 When adjusting the temperature press the UP DOWN arrow ke...

Страница 14: ... Main User Menu 1 Press the NO key for all prompts until the Cancel ovrd prompt appears If the controller is in the override state this is the first prompt 2 Press the YES key to resume the programmed schedule The controller returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User Menu of the controller when in the Occupied state sets ...

Страница 15: ...ss the NO key for all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES key to change the Occupied cooling setpoint Press the NO key to advance to the Occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to store the value and advance t...

Страница 16: ...te The setting for the Fan cont parameter may affect the fan operation on a call for heating Table 5 Entering Humidity Setpoints Controller Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key for all prompts until the humidity setpoint prompt appears on the display Press the YES key to enter the humidity setting menu Press the YES ke...

Страница 17: ...he fan mode prompt appears on the display Press the YES key to enter the fan mode setting menu Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the desired system mode example for smart mode shown Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu RoomTemp 75 0 F Fan mode set Y N Fan mode Sma...

Страница 18: ...s on the display Press the YES key to enter the scheduling menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Table 8 Programming the Daily Schedule Two Event Part 2 of 2 Controller Display Description Exit Y N RoomTemp 75 0 F Schedule set Y N Monday set Y N Press the YES key to set the Occupied start time for Monday or press the NO key to advance to Tu...

Страница 19: ...P M 1 Sunday 12 00 P M 1 12 00 P M 1 12 00 P M 1 12 00 P M 1 1 Programming different events to the same time for that day cancels those events and leaves the controller in the Unoccupied state Table 11 Setting the Day and Time Part 1 of 2 Controller Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key for all prompts until the clock s...

Страница 20: ...edule hold menu has the following selections Permanent Occupied Hold occ hold This selection puts the controller into a permanent Occupied state via the Occupied setpoints Occupied hold appears in the Status Display Menu when this selection is active Permanent Unoccupied Hold This selection puts the controller into a permanent Unoccupied state via the Unoccupied setpoints Unoccup hold appears in t...

Страница 21: ...ted on the wall Remote duct mounted humidity sensor may be used for remote return air humidity sensing with the sensor mounted on the return air duct or as a supply air humidity sensor used as a high limit protection 2 Additional TE 636xx x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available refer to the TE 6300 Series Temperature Sensors Product Bulletin LIT 216320 for more d...

Страница 22: ...ents Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Humidity 5 RH from 30 to 70 RH at 50 to 90 F 10 to 32 C Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Non...

Отзывы: