T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
16
Entering Humidity Setpoints
You can enter setpoints for humidification and
dehumidification after configuring the temperature
setpoints. A fixed 5% RH deadband is present between
the humidification and dehumidification to prevent
overlap in these humidity setpoints. For example, if the
humidification setpoint is 50% RH and the
dehumidification setpoint is changed from 70% RH to
45% RH, the humidification setpoint is automatically
changed to 40% RH by the controller.
To enter humidity setpoints, follow the steps in Table 5.
Selecting the System Mode
The controller has four system modes:
•
Automatic Mode (auto):
Automatic changeover
between heating and cooling. This is the default
setting.
•
Cooling Mode (cool):
Cooling operation only.
•
Heating Mode (heat):
Heating operation only.
•
Off Mode (off):
The controller is off; however,
when the frost protection (
Frost pr
parameter) is
enabled, the controller still calls for heat if the
temperature falls below 42°F/5.5°C.
To set the system mode, follow the steps in Table 6:
Selecting the Fan Mode
The controller has three fan mode settings:
•
On Fan Mode (on):
Energizes the fan all the time
for both Occupied and Unoccupied states, even if
the system mode is set to off.
•
Automatic Fan Mode (auto):
Energizes the fan
only on a call for heating or cooling, for both
Occupied and Unoccupied states. This is the
default setting for the T606MSN-4 and
T606MSN-4+PIR models.
Note:
The setting for the
Fan cont
parameter may
affect the fan operation on a call for heating.
Table 5: Entering Humidity Setpoints
Controller
Display
Description
Press the
MENU
key while in the
Status Display Menu to enter the
Main User Menu.
Press the
NO
key for all prompts until
the humidity setpoint prompt appears
on the display. Press the
YES
key to
enter the humidity setting menu.
Press the
YES
key to change the
dehumidification setpoint. Press the
NO
key to advance to the
humidification setpoint menu.
Press the
UP/DOWN
arrow keys to
set the dehumidification setpoint.
Press the
YES
key to store the value
and advance to the next menu.
Press the
YES
key to change the
humidification setpoint. Press the
NO
key to advance to the next menu.
Press the
UP/DOWN
arrow keys to
set the humidification setpoint. Press
the
YES
key to store the value and
advance to the next menu.
Press the
YES
key to return to the
Status Display Menu or press the
NO
key to re-enter the humidity
setting menu.
RoomTemp
75.0
°
F
Humidity
set? Y/N
Dehumidi
set? Y/N
Dehumidi
70 %
Humidifi
set? Y/N
Humidifi
50 %
Exit?
Y/N
Table 6: Selecting the System Mode
Controller
Display
Description
Press the
MENU
key while in the
Status Display Menu to enter the
Main User Menu.
Press the
NO
key for all prompts
until the system mode prompt
appears on the display. Press the
YES
key to enter the system mode
setting menu.
Press the
UP/DOWN
arrow keys to
locate the desired system mode.
Press the
YES
key to select the
desired system mode (example for
auto mode shown)
Press the
YES
key to return to
the Status Display Menu or press
the
NO
key to return to the
system mode selection menu.
RoomTemp
75.0
°
F
Sys mode
set? Y/N
Sys mode
auto
Exit?
Y/N