RRS Economizer Controller Quick Start Guide
1
RRS Economizer Controller
Quick Start Guide
5292230-USG-B-0718
FIGURE 1 -
RRS Economizer Controller
Field-installed economizer accessories with the RRS Econo-
mizer Controller utilize the P12/S12 connector for inter-con-
necting wiring to the 3 through 6 ton units equipped with
Simplicity Lite in the same manner as Honeywell W7212 and
Jade controllers in economizer accessories. Through the
P12/S12 connector, the unit-to-RRS Economizer wiring con-
nections are as follows:
• TB1 to RRS Economizer Controller C pin -
Pro-
vides cabinet ground-referenced 24 volts AC com-
mon to power the RRS Economizer Controller,
economizer inputs and outputs
• Simplicity Lite G pin to RRS Economizer Con-
troller R pin -
Provides 24 volts AC hot to power
the RRS Economizer Controller, economizer
inputs and outputs when Simplicity Lite operates
the indoor blower
•
Simplicity Lite OCC pin to RRS Economizer
Controller OCC pin
- 24 volts AC originating from
jumper or thermostat input to the Simplicity Lite
OCC screw terminal, through the Simplicity Lite
OCC output pin to the RRS Economizer Controller
•
Simplicity Lite Y1 pin to RRS Economizer Con-
troller Y1 pin
- 24 volts AC originating from ther-
mostat input to the Simplicity Lite Y1 screw
terminal, through the Simplicity Lite Y1 output pin
to the RRS Economizer Controller Y1 pin input
indicates there is a first stage cooling request
•
RRS Economizer Controller Y1O pin to Sim-
plicity Lite ECON pin
- 24 volts AC from the RRS
Economizer Controller Y1O pin output to the Sim-
plicity Lite ECON pin input allows initiation of com-
pressor operation when outdoor conditions are
not suitable for free cooling
FIGURE 2 -
Simplified Diagram Of RRS Economizer
Control To 3 Through 6 Ton Unit Wiring
Connections
Y1
G
OCC
ECON
C
R
Y2
O
Y1
O
Y2
Y1
OC
C
W1
C
R
DF
B
DM
P
í
+
24 VAC Common for Economizer
Controller Power/Inputs/Outputs
Simplicity Lite
TB1
On with Simplicity Lite blower operation – 24 VAC
Hot for Economizer Controller Power/Inputs/Outputs
From 24 VAC thermostat input to Simplicity
Lite – 1
st
Stage Cooling Request
From 24 VAC jumper/thermostat input to
Simplicity Lite – Occupancy Indication
24 VAC compressor request to Simplicity Lite with
1
st
Stage Cooling Request & Free Clg Avail = No