5292230-USG-B-0718
RRS Economizer Controller Quick Start Guide
11
operation, the trend timestamp has limited practical use in 3
through 6 ton package units because the RRS Economizer
Controller is powered only when the indoor fan operates.
FIGURE 26 -
Indication That The USB Flash Drive Is
Not Connected Or Incompatible
A “USB Missing” message will be shown when the
(enter)
button is pressed when at (Level 1) “Update” > (Level 2)
“ExportTrend” location of the display menu without a compat-
ible flash drive connected to the USB port. A press of the esc
(cancel)
(scroll up) or
(scroll down) button will then
resume menu navigation.
FIGURE 27 -
Exporting A Trend
With a compatible flash drive connected to the USB port, the
(enter) button is pressed when at (Level 1) “Update” >
(Level 2) “Export Trend” location of the display menu.
While the Export Trend is in progress, “Exporting” will be
shown on the upper line of the display.
In approximately 5 seconds; “Export” on the upper line and
“Done” will be shown on the lower line of the display when the
Export Trend function is complete. The flash drive may be
then be removed from the USB port if not needed for other
functions. A press of the esc (cancel),
(scroll up) or
(scroll down) button will then resume menu navigation.
FIGURE 28 -
Windows PC view of Firmware Upgrade,
Restoration, Self Test Report and Trend
Files on a Flash Drive
Table 1: RRS Economizer Controller Trending
Value
Sample Interval
Max Samples
SAT
5 minutes
2016
RAT
10 minutes
1008
OAT
15 minutes
672
OAH
15 minutes
672
RAH
10 minutes
1008
IAQ
15 minutes
672
Y1
status change
100
Y2
status change
100
W1
status change
100
Shutdown
status change
100
OCC
status change
100
Blackout
status change
100
Brownout
status change
100
Y1Out
status change
100
Y2Out
status change
100
AlarmOut
status change
100
ERV
status change
100
EconType
status change
100
OAEnthalpy
15 minutes
672
RAEnthalpy
10 minutes
1008
FreeClgAvail
status change
100
StartupDelayState
status change
100
ExhaustControlState
status change
100
ClgAvailState
status change
100
ExcessiveSATState
status change
100
TstatSequencerState
status change
100
OADamper
status change
800
DamperFeedback
status change
800
DamperPropBand
status change
200
DamperIntegralTime
status change
200
esc
USB
Missing
esc
esc
esc
Restore
>Export Trend
Exporting
Export
Done