IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
103
Abort Switches
Releasing Applications
2.
The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 17 seconds, more than the original 15 second FACP Delay Timer
countdown.
3.
The FACP programmed Delay Time is not running (as would happen if the releasing station
were pulled before an alarm registered). The Manual Release Delay Switch is activated by the
pull station. Agent release will occur in 10 seconds.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...