50
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Point Program
Point Programming (2) - Control
Figure 3.37 Panel Module Point Programming (2) -Control - Screen
Soft Keys
ZONE MAP:
Displays the zones mapped to this point. The default value assigned to panel circuit
output modules during initial programming is Z000, with the exception of control modules with the
following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend. . To
add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, logic, release,
special or trouble zones may be mapped to a panel control module.Position 1 has additional
functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST:
This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). The default is OFF.
NOTE:
The IZM-8RK module does not participate in Walk Test. Also, the following Type ID
codes do not participate in Walk Test, and the
WALK
TEST
soft key will not appear when the
screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, RELEA.FORM C, REL
AUDIBLE, INSTANT RELE, NONRESET CTL, and TELEPHONE.
SILENCEABLE:
This field determines whether the user can manually silence an activated output.
Values are YES - RESOUND FIRE (manually silenceable, resounds on fire alarm) and NO (not
manually silenceable). The default is YES.
NOTE:
This soft key will not appear for modules with Type ID codes where silence is not
optional.
SWITCH INHIBIT:
This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). The default is
NO.
P A N E L M O D U L E P O I N T P R O G R A M M I N G
P 1 1 . 2
Z O N E M A P :
Z 0 0 0
, Z 1 0 4
, Z 1 0 5
, Z 1 0 6
, Z 1 0 7
Z 1 1 0
, Z 1 1 4
, Z 1 1 5
, Z 1 1 6
, Z 1 1 7
W A L K T E S T : O F F
S W I T C H I N H I B I T : Y E S
A C C E P T
S I L E N C E A B L E : Y E S - R E S O U N D F I R E
B A C K
Zone Map Position 1 - Use for group zone
disable participation.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...