IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
131
Appendix F: Detector Initialization
F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.
WARNING:
If any detector is replaced with a different type of detector (for example, a laser detector is replaced
with a photoelectric detector), the control panel must be programmed immediately with the new
detector Type Code. Failure to do so can cause incorrect control panel operation, including false
alarms.
F.2 To Replace a Detector with a Different Type of Detector
If one type of detector is replaced with a different type of detector, the control panel must
immediately be programmed for the new detector type. To replace a detector, follow these steps:
NOTE:
The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds.
Step
Action
1
Delete the old detector point from FACP programming using the “Delete Point” screen on
page page 57.
2
Physically remove the old detector.
3
Enter point programming for this point and change the Type and FlashScan Code Label to
the values appropriate for the new detector. (Refer to “Detector Point” on page 38 for
programming instructions).
4
Physically install the new detector. Initialization will occur automatically
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...