70
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Alter Status
Walk Test
Figure 4.8 Clear History Screen
Soft Keys
ALARM HISTORY:
Press to clear Alarm history.
EVENT HISTORY:
Press to clear Event history.
ALL HISTORY:
Press to clear both Alarm and Event history.
4.6 Walk Test
Walk Test allows the user to test the entire fire alarm system while away from the control panel.
There are two types of Walk Test - Basic and Advanced - and each type operates in audible mode.
Walk Test results are sent to the printer and to Event History as “Test”.
IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the
ABORT
soft key on the screen
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
C L E A R H I S T O R Y
A L A R M H I S T O R Y
E V E N T H I S T O R Y
A L L H I S T O R Y
B A C K
!
WARNING:
Physically disconnect all releasing devices before starting Walk Test. It is not
sufficient to disable in any other manner.
!
WARNING:
Walk Test mode can deactivate fire protection. Observe the following important
precautions.
NOTE:
Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...