IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
89
Appendix B: Releasing Applications
B.1 Releasing Zones
The control panel includes ten releasing zones (ZR00-ZR09) that can be used to control up to ten
releasing operations. Each zone operates independently, and is fully programmable. To program a
releasing zone, refer to “Releasing Zone” on page 51.
There are four releasing functions, outlined below, that can be defined by entering values in the
associated fields during programming.
!
WARNING:
Do not rely on Disable to disable releasing points during testing. Releasing points
must be physically disconnected.
Function/Field
Explanation
Delay Time
Delay Time is the time that elapses between activation of an initiating device and
activation of all outputs mapped to the initiating device through a releasing zone.
Delay Time can have a value of 0 to 60 (seconds). A value of 0 will result in immediate
output activation upon activation of the initiating device.
Following is a graphic representation of what happens when a delay timer is set to 15
seconds for releasing zone ZR02.
NOTE:
If cross-zoning is in effect, the delay time will not begin until the
cross-zoning conditions are met. Refer to “Cross Zones” on page 97 for
more information.
Abort Switch
Selection of a 3-letter abort switch type code (ULI, IRI, NYC, or AHJ) defines the
operation of an Abort Switch in that releasing zone. Refer to the specific abort switch
type code heading in this appendix for details on how each functions.
Cross Zone
Select one of three Cross Zone types (Yes, Zone, or Heat), or No (not used). A Cross
Zone requires tripping two or more initiating devices to activate the outputs mapped to a
releasing zone. Refer to the Section B.3.5 on page 97 section of this appendix for details
and examples.
Soak Time
(NFPA 16
Applications
only)
Soak Time specifies the length of time to dump releasing agents when a releasing zone
activates. When the Soak Time expires, the control panel automatically shuts the
releasing solenoids for the active releasing zone. Soak Time can have a value of 0 to
9999 seconds. If Soak Time is set to 0, the releasing solenoids will remain active until
system reset.
Following is a graphic representation of what happens when soak time is set to 300
seconds for releasing zone ZR02.
Initiating device with
releasing zone
ZR02 in its zone
map activates
All outputs with
ZR02 in their zone
maps activate at
15 seconds
Delay Time = 15 (seconds)
0 sec.
15
sec.
Initiating device
with releasing
zone ZR02 in its
zone map
activates. All
outputs with ZR02
in their zone maps
At 300
seconds, the
control panel
shuts releasing
solenoids for
outputs with
Soak Time = 300 (seconds)
0
sec.
300 sec.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...